Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903 Catalog No. 530-930 Printed in U.S.A. Form 09/30/38-6SI Pg 1 506 10-03 Replaces: 09/30/38-5SI
Book 122
Tab 3a4a5c
Installation and Start-Up Instructions
Part Numbers: 30GT-911---074, 30GT-911---075, 30GT-911---076,
30GT-911---077, 30GT-911---078, 30GT-911---079, 30GT-911---080,
30GT-911---081, 30GT-911---082
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
APPLICATION NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5
Winter Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
Step 1— Install Field-Fabricated
Wind Baffles and Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Step 2 — Mount Motormaster V Controls
and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
MOTORMASTER V CONTROLLERS, FUSE
BLOCK RELAYS AND FUSES
PRESSURE TRANSDUCER
Step 3 — Make Electrical Connections. . . . . . . . . . . . . . . . .11
09DK054-094, 30GTN,GTR,GUN,GUR040-110,
230B, 245B, 38AH044-104 (Except Single Circuit)
38AH024-034, 38AKS028-044, 09DK020-044
38AH044-084 SINGLE CIRCUIT AND 124A/B, 134A/B
30GTN,GTR,GUN,GUR130-210, 230A-315A,
330A/B-420A/B
Step 4 — Configure Motormaster V Control. . . . . . . . . . . 24
Step 5 — Configure Unit for Motormaster V
Operation, 30GTN,GTR,GUN,GUR Only . . . . . . . . . . . . . 24
Step 6 — Test Motormaster V Control. . . . . . . . . . . . . . . . . 24
START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25,26
Drive Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27,28
EPM Chip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Liquid Line Pressure Set Point Adjustment . . . . . . . . . . . 27
Loss of CCN Communications. . . . . . . . . . . . . . . . . . . . . . . . 27
SAFETY CONSIDERATIONS
Installation, start-up, and servicing of this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment and any other safety precautions that may apply.
INTRODUCTION
This book contains instructions for the installation and
start-up of the Motormaster V (MMV) control on models
09DK (100%, 50%/50% and 67%/30% split only), 30GTN,
GTR,GUN,GUR040-420, 38AH044-134, and 38AKS028-044.
The 30GTN,GTR,GUN,GUR230-420 units are shipped as 2
separate modules. See Table 1 for details of modular units.
Two Motormaster Accessory Packages are required for
modular units.
Table 1 — 30GTN,GTR,GUN,GUR080-210 and
Associated Modular Units
The Motormaster V control is a motor speed control device
that adjusts condenser fan motor speed in response to declining
liquid refrigerant pressure. A properly applied Motormaster V
control extends the operating range of air-conditioning systems
and permits operation at lower outdoor ambient temperatures.
On 09DK units, the Motormaster V control is used in con-
junction with the standard fan cycling controls. See Table 2A
or 2B for the ambient temperatures at which the 09DK units
operate without modification.
Motormaster V control cannot be installed with the high-
static fan option.
Table 2A — Minimum Outdoor-Air Operating
Temperature — 09DK (English)
NOTE: See Legend and Notes on page 2.
Open all remote disconnects before servicing this equip-
ment. Electrical shock could result in personal injury.
UNIT
30GTN,GTR,GUN,GUR
ASSOCIATED UNIT MODULES
30GTN,GTR,GUN,GUR
080 230B
090 245B
100 255B, 270B
110 290B, 315B
130 None
150 230A-255A
170 270A, 330A/B, 360B (50 Hz)
190 290A, 360A, 360B (60 Hz), 390B
210 315A, 390A, 420A/B
UNIT
09DK
HEAD
PRESSURE
CONTROL
TD
(F)
COMPRESSOR CAPACITY
(%)*
100 75 50 25
Minimum Outdoor-Air
Temperature (F)
020,024,
028
FCPSs (1 Fan)†
30 29 34 38 51
25 38 40 42 53
20 47 47 46 56
034,044 FCPSs (2 Fans)†
30 12 19 22 43
25 22 25 29 47
30 31 31 36 51
054,064 FCPSs (2 Fans)†
30 29 34 38 51
25 38 40 42 53
20 47 47 46 56
074-094
FCPSs (2 Fans)†
ATSs (2 Fans)
30 12 19 22 43
25 22 25 29 47
20 31 31 36 51
09DK020-094
30GTN,GTR,GUN,GUR040-420/38AH024-134/38AKS028-034
Accessory Low Ambient Operation
Motormaster® V Control
50/60 Hz
Vista de pagina 0
1 2 3 4 5 6 ... 27 28

Indice de contenidos

Pagina 1 - 50/60 Hz

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Pagina 2

10LEGENDTYP — Typ i ca lNOTE: Dimensions in ( ) are millimeters.Fig. 9 — “C,” “D,” and “E” Baffles for 30GTN,GTR,GUN,GUR130-210, 230A-315A, 330A/B-420

Pagina 3

11Step 2 — Mount Motormaster® V Controls andAccessoriesNOTE: Two Motormaster V controllers, 2 fuse blocks, 2 relaysand 2 pressure transducers must be

Pagina 4 - APPLICATION NOTES

1238AH024-034, 38AKS028-044 and 09DK020-044 (SeeFig. 25)1. Mark the shielded cable from FM1 to FC1 at Motor-master® V controller location. The cable w

Pagina 5 - INSTALLATION

13GND — GroundMM — Motormaster ControlMMF — Motormaster RelayNEC — National Electrical CodeTB — Terminal BlockTRAN — Transformer09DK054,064 09DK074-09

Pagina 6

14Fig. 12 — Motormaster® V Control Location; 38AH024-034, 38AKS028-044Fig. 13 — Motormaster V Control Location; 09DK020-044

Pagina 7

1513141314RELAYFUSE BLOCK1212CONTROLBOXCONTROLBOX30GTN,GTR,GUN,GUR080,090;MODULES 230B,245B/38AH094,10430GTN,GTR,GUN,GUR100,110;MODULES 255B,315BMOTOR

Pagina 8

161212CONTROLBOXCONTROLBOX30GTN,GTR,GUN,GUR080,090;MODULES 230B,245B/38AH094,10430GTN,GTR,GUN,GUR100,110;MODULES 255B,315BFUSEBLOCKRELAYMOTORMASTER VA

Pagina 9 - Low Ambient Operation

1713141314RELAYFUSE BLOCKMOTORMASTER VACCESSORY LEGENDFC — Fan ContactorFCB — Fan Circuit BreakerFR — Fan RelayMM — Motormaster® ControlMMF — Motormas

Pagina 10

18MMPT-A & MMPT-BCABLE ROUTINGTRANSDUCER MMPT-B (040-110) MMPT-A (130-210)FROM CORRESPONDING MMV (VFD) IN CONTROL BOXTRANSDUCER MMPT-A (040-110) M

Pagina 11 - Accessories

19Fig. 18 — 38AH Dual-Circuit Pressure Transducer Location

Pagina 12

2Table 2B — Minimum Outdoor-Air Operating Temperature — 09DK (SI)LEGEND*Interpolation permitted.†Additional FCPS required for 66%/33%.NOTES:1. Fans on

Pagina 13 - (074-094 Units Shown)

20Fig. 19 — Typical Piping for 09DK Condenser With a Dual Split System*Field supplied.NOTES:1. Hot gas lines should rise above refrigerant level incon

Pagina 14

21Fig. 22 — 38AH Single-Circuit Pressure Transducer LocationMOUNTTRANSDUCERSON LIQUID LINESERVICE VALVEUSING TEESSUPPLIED IN KITCOMPRESSOR END, RIGHT-

Pagina 15 - 30GTN,GTR,GUN,GUR100,110;

22MOTORMASTER V ACCESSORY100%, 50%/50% AND 67%/33%CAPACITY SPLITS ONLYMOTORMASTER V ACCESSORYFig. 23 — 09DK054-094 Schematic DiagramFig. 24 — 38AH044-

Pagina 16

23MOTORMASTER V ACCESSORYMOTORMASTER V ACCESSORYFig. 26 — 38AH Single Circuit 044-084, 124A/B, 134A/B Schematic DiagramLEGENDFCB — Fan Circuit Breaker

Pagina 17 - Component Arrangement

24Step 4 — Configure Motormaster® V Control —The Motormaster V control is configured for 1 of 12 operationmodes based on the inputs to the small termi

Pagina 18 - MM — Motormaster® Control

25START-UPWhen the system calls for the fan, the fan relay will be ener-gized to start the Motormaster® V electronic control. The LEDwill display the

Pagina 19

26Table 9 — Motormaster® V Program Parameters for Operating Modes LEGENDPARAMETERS DESCRIPTIONMODE 1MODE 2MODE 3MODE 4MODE 9MODE

Pagina 20 - CIRCUIT NO. 1

27TROUBLESHOOTINGTroubleshooting the Motormaster® V control requires acombination of observing system operation and VFD displayinformation. Refer to T

Pagina 21

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Pagina 22 - CAPACITY SPLITS ONLY

3Table 5 — Motormaster® V Control Package ContentsAWG — American Wire GageNOTE: The 09DK020 also requires a field-supplied, 20 x 20 x 8 NEMA 3R enclos

Pagina 23

4Table 6 — Applicable Voltages and Motors*Not all voltages are available for all units. See base unit installation instruc-tions for available voltage

Pagina 24

5Winter Start — All 30GTN,GTR,GUN,GUR chillers havewinter start features included in their microprocessor controllogic. All 38AH and 38AKS units have

Pagina 25 - START-UP

6LEGENDTYP — Typ i ca lNOTES:1. Dimensions in ( ) are millimeters.2. All units listed as modules consist of onemodule “A” plus one module “B.”Fig. 3 —

Pagina 26

7LEGENDTYP — Ty pi c a lNOTES:1. Dimensions in ( ) are millimeters.2. All units listed as modules consist of onemodule “A” plus one module “B.”LEGENDT

Pagina 27 - TROUBLESHOOTING

8LEGENDTYP — Typ i ca lNOTES:1. Dimensions in ( ) are millimeters.2. All units listed as modules consist of onemodule “A” plus one module “B.”09DK054,

Pagina 28 - Table 11 — Fault Codes

9Summary of Baffles and Brackets*See Fig. 10 for bracket construction.†Total unit (includes both modules).NOTE: See Fig. 9 for baffle construction.UNI