58MXA4-Way Multipoise Fixed-CapacityDirect-Vent Condensing Gas FurnaceService and Maintenance Instructions→ For Sizes 040—140, Series 130NOTE: Read th
NOTE: Heat tape, when used, should be wrapped around thecondensate drain trap and drain line. There is no need to use heattape within the furnace casi
PCBBLOWER OFF DELAYSELECTION CHART90 SEC135 SEC180 SEC225 SECGVRHI/LORELAYSEC-1SEC-2WHTPL1321654987LEDTEST/TWINBLOWEROFFDELAYGRYWCHUMHSIR IDR BLWRBLOW
→ Fig. 16—Service LabelA99107SERVICECOMPONENT TESTTo initiate the component test sequence,shut OFF the room thermostat ordisconnect the "R"
Is circuit breaker closed?Close door switch and go to start.Is red LED status light on? Is door switch closed?Is red LED status light blinkingrapidly
11 NO PREVIOUS FAULT - Faultsare erased after 48 hrs orwhenever power (115v or 24v) isinterrupted. Run system througha heating or cooling cycle toche
15
A94328SERVICE TRAININGPackaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, in
The ability to properly perform maintenance on this equip-ment requires certain expertise, mechanical skills, tools, andequipment. If you do not posse
Step 1—Cleaning and/or Replacing Air FilterThe air filter arrangement may vary depending on the applicationor orientation.Never operate unit without a
11. Reinstall condensate trap and tubing if previously removed.a. Reinstall condensate trap in hole in blower shelf.b. Connect condensate trap drain t
Never use matches, candles, flame, or other sources ofignition to check for gas leakage. Use a soap-and-watersolution. Failure to follow this warning
Never use matches, candles, flame, or other sources ofignition to check for gas leakage. Use a soap-and-watersolution. Failure to follow this warning
4. Disconnect pressure switch tubes.5. Disconnect vent pipe from inducer housing outlet by loosen-ing coupling clamp on inducer outlet.6. Disconnect d
10. Replace main furnace door.Step 7—Electrical Controls and WiringThere may be more than 1 electrical supply to the unit. Checkaccessories and coolin
1. Leave 115-v power to furnace turned on.2. Remove main furnace door.3. Look into blower access panel sight glass for current LEDstatus.NOTE: Leave b
Comentarios a estos manuales