Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 903 Catalog No. 533-00047 Printed in U.S.A. Form 30RA-2T Pg 1 1-03 Replaces: 30RA-1T
Book 2
Ta b 5 c
Controls, Start-Up, Operation,
Service, and Troubleshooting
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roof, elevated structures, mechanical
rooms, etc.). Only trained, qualified installers and service
mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment, and any other safety precautions that apply. Follow
all safety codes. Wear safety glasses and work gloves. Use
care in handling, rigging, and setting this equipment, and in
handling all electrical components.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation and
service. There may be more than one disconnect switch.
Tag all disconnect locations to alert others not to restore
power until work is completed.
DO NOT VENT refrigerant relief valves within a building.
Outlet from relief valves must be vented outdoors in
accordance with the latest edition of ANSI/ASHRAE
(American National Standards Institute/American Society
of Heating, Refrigeration and Air Conditioning Engineers)
15 (Safety Code for Mechanical Refrigeration). The
accumulation of refrigerant in an enclosed space can
displace oxygen and cause asphyxiation. Provide adequate
ventilation in enclosed or low overhead areas. Inhalation of
high concentrations of vapor is harmful and may cause
heart irregularities, unconsciousness or death. Misuse can
be fatal. Vapor is heavier than air and reduces the amount
of oxygen available for breathing. Product causes eye and
skin irritation. Decomposition products are hazardous.
DO NOT attempt to unbraze factory joints when servicing
this equipment. Compressor oil is flammable and there is
no way to detect how much oil may be in any of the
refrigerant lines. Cut lines with a tubing cutter as required
when performing service. Use a pan to catch any oil that
may come out of the lines and as a gage for how much oil
to add to system. DO NOT re-use compressor oil.
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from recom-
mended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the electronic
modules or electrical components.
To prevent potential damage to heat exchanger, always run
fluid through heat exchanger when adding or removing
refrigerant charge. Use appropriate brine solutions in cooler
fluid loop to prevent the freezing of brazed plate heat
exchanger, optional hydronic section and/or interconnecting
piping when the equipment is exposed to temperatures
below 32 F (0 °C). Proof of flow switch and strainer are
factory installed on all models. Do NOT remove power
from this chiller during winter shutdown periods without
taking precaution to remove all water from heat exchanger
and optional hydronic system. Failure to properly protect
the system from freezing may constitute abuse and may
void warranty.
Compressors and optional hydronic system pumps require
specific rotation. Test condenser fan(s) first to ensure
proper phasing. Swap any two incoming power leads to
correct condenser fan rotation before starting any other
motors.
Refrigerant charge must be removed slowly to prevent loss
of compressor oil that could result in compressor failure.
30RA010-055
AquaSnap® Air-Cooled Chillers
with ComfortLink™ Controls
50/60 Hz
Vista de pagina 0
1 2 3 4 5 6 ... 99 100

Indice de contenidos

Pagina 1 - Service, and Troubleshooting

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Pagina 2 - CONTENTS

10Fig. 4 — Wiring Schematic 30RA022-03030RA022-030 AQUA SNAP

Pagina 3

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Pagina 4 - Sensors —

11Fig. 4 — Wiring Schematic 30RA022-030 (cont)AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (022-030)

Pagina 5

12Fig. 5 — Wiring Schematic 30RA032-04030RA032-040 AQUA SNAP

Pagina 6

13Fig. 5 — Wiring Schematic 30RA032-040 (cont)AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (032-040)

Pagina 7

14Fig. 6 — Wiring Schematic 30RA042-05530RA042-055 AQUA SNAP

Pagina 8 - 30RA010-018 AQUA SNAP

15Fig. 6 — Wiring Schematic 30RA042-055 (cont)AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (042-055)

Pagina 9 - SEE NOTE 8

16CEPL130346-01STATUSLENJ1J2J4J3J5J6J7J8J9J10CCNRED LED - STATUS GREEN LED -LEN (LOCAL EQUIPMENT NETWORK)YELLOW LED -CCN (CARRIER COMFORT NETWORK)INST

Pagina 10 - 30RA022-030 AQUA SNAP

17Energy Management Module (Fig. 11) — Thisfactory-installed option (FIOP) or field-installed accessory isused for the following types of temperature

Pagina 11

18Table 6 — Part Load Data Percent Displacement, Standard Units without Minimum Load ValveNOTE: These capacity steps may vary due to different capacit

Pagina 12 - 30RA032-040 AQUA SNAP

19Table 7 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve*Minimum Load Valve energized.NOTE: These capacity steps may va

Pagina 13

2CONTENTSPageSAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . . . . 1GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 14 - 30RA042-055 AQUA SNAP

20MINUTES LEFT FOR START — This value is displayedonly in the network display tables (using Service Tool,ComfortVIEW™ or ComfortWORKS® software) an

Pagina 15

21Head Pressure Control — The Main Base Board(MBB) controls the condenser fans to maintain the lowestcondensing temperature possible, and thus the hig

Pagina 16 - Fig. 7 — Main Base Board

22Operation of Machine Based on ControlMethod and Cooling Set Point Selection Set-tings — Machine On/Off control is determined by theconfiguration of

Pagina 17 - Capacity Control —

23Table 8 — Control Methods and Cooling Set Points*Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input

Pagina 18 - CEPL130351-01

24Optional Factory-Installed Hydronic Package —If the chiller has factory-installed chilled fluid pumps, specificsteps should be followed for proper o

Pagina 19

25Opened During Normal Operation Alarm will be generatedand the machine will stop. If the control detects the chilled water pump interlock openfor 25

Pagina 20 - Leaving Water Temperature

26As part of a pump maintenance routine, the pumps can bestarted to maintain lubrication to the pump seal. To utilize thisfunction, Cooler Pmp Periodi

Pagina 21 - Head Pressure Control —

27Table 10 — Run Status Mode and Sub-Mode DirectoryNOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except

Pagina 22 - DETAIL A

28Table 10 — Run Status Mode and Sub-Mode Directory (cont)*Press and simultaneously to obtain version number.SUB-MODEKEYPADENTRYITEM DISPLAY SUB-ITEM

Pagina 23 - Tables 8-27) —

29Table 11 — Service Test Mode and Sub-Mode DirectoryNOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, excep

Pagina 24 - Cooler Pump Control —

3Table 1 — Unit Sizes *60 Hz only.†50 Hz only.MAJOR SYSTEM COMPONENTSGeneral — The 30RA air-cooled reciprocating chillerscontain the ComfortLink™ elec

Pagina 25

30Table 13 — Pressure Mode and Sub-Mode DirectoryNOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except th

Pagina 26

31Table 16 — Outputs Mode and Sub-Mode DirectoryNOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the

Pagina 27

32Table 17 — Configuration Mode and Sub-Mode Directory (cont)SUB-MODEKEYPADENTRYITEM DISPLAYITEMEXPANSIONCOMMENTOPT1UNIT OPTIONS 1 HARDWAREFLUD X COOL

Pagina 28

33Table 17 — Configuration Mode and Sub-Mode Directory (cont)SUB-MODEKEYPADENTRYITEM DISPLAYITEMEXPANSIONCOMMENTRSET (cont)RM.FXXX.X °FREMOTE - FULL R

Pagina 29

34Table 18 — Time Clock Mode and Sub-Mode DirectorySUB-MODEKEYPADENTRYITEM DISPLAY SUB-ITEM DISPLAYITEMEXPANSIONCOMMENTTIME TIME OF DAYHH.MM XX.XX HOU

Pagina 30

35Table 18 — Time Clock Mode and Sub-Mode Directory (cont)SUB-MODEKEYPADENTRYITEM DISPLAY SUB-ITEM DISPLAYITEMEXPANSIONCOMMENTSCH.L (cont) PER.3 OCC

Pagina 31

36Table 18 — Time Clock Mode and Sub-Mode Directory (cont)SUB-MODEKEYPADENTRYITEM DISPLAY SUB-ITEM DISPLAYITEMEXPANSIONCOMMENTSCH.L (cont) THU.6 YES/N

Pagina 32

37Table 19 — Operating Mode and Sub-Mode DirectoryLEGENDTable 20 — Alarms Mode and Sub-Mode DirectorySUB-MODEKEYPADENTRYITEM DISPLAYITEMEXPANSIONCOMME

Pagina 33

38Table 21 — Dual Chiller Configuration (Master Chiller Example)SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTSDISPUNITOPT1OPT2 CTRL CONTRO

Pagina 34

39Table 21 — Dual Chiller Configuration (Master Chiller Example) (cont)NOTES:1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupanc

Pagina 35

4At each system element, the shields of its communicationbus cables must be tied together. If the communication bus isentirely within one building, th

Pagina 36

40Table 2 2 — Dual Chiller Configuration (Slave Chiller Example)NOTES:1. Slave Control Method (CTRL) must be configured for 0.2. Slave CCN Address (CC

Pagina 37

41Table 23 — Operating ModesMODE NO. ITEM EXPANSION DESCRIPTION01FSM CONTROLLING CHILLER Flotronic™ System Manager (FSM) is controlling the chiller.

Pagina 38

42Table 24 — Example of Reading and Clearing AlarmsTable 25A — 4-20 mA ResetNOTE: The example above shows how to configure the chiller for 4-20 mA res

Pagina 39

43Table 26A — Configuring Outdoor Air and Space Temperature Reset*4 items skipped in this example.Table 26B — Configuring Return Temperature Reset*4 i

Pagina 40

442.0 F (1.1 C) cooler ∆T and 0° F (0° C) reset at 10.0 F (5.6 C)cooler ∆T. The variable RT.NO should be set to the coolertemperature difference (∆T)

Pagina 41 - Table 23 — Operating Modes

45DEMAND LIMIT (CCN Loadshed Controlled) — To con-figure Demand Limit for CCN Loadshed control set the De-mand Limit Select (DMDC) [Configuration, RS

Pagina 42 - Table 25A — 4-20 mA Reset

46Table 27 — Configuring Demand Limit*Seven items skipped in this example.TROUBLESHOOTINGComplete Unit Stoppage and Restart — Possi-ble causes for u

Pagina 43

47Table 28 — Troubleshooting SYMPTOMS CAUSE REMEDYCooler Circulating Pump DoesNot RunPower line open Reset circuit breaker.Control fuse or circuit bre

Pagina 44 - Demand Limit —

48Fig. 22 — Component Arrangement — 30RA010-030LEGENDC — Contactor, CompressorCB — Circuit BreakerCHC — Cooler/Pump Heater ContactorCWP — Chilled Wate

Pagina 45 - Energy Management Module

49Fig. 23 — Component Arrangement — 30RA032-040LEGENDC — Contactor, CompressorCB — Circuit BreakerCHC — Cooler/Pump Heater ContactorCWP — Chilled Wate

Pagina 46 - ENTER ENTER

5T10 — REMOTE SPACE TEMPERATURE SENSOR ORDUAL LEAVING WATER TEMPERATURE SENSOR —One of two inputs can be connected to TB5-5 and TB5-6. Seeappropriate

Pagina 47 - Table 28 — Troubleshooting

50Fig. 24 — Component Arrangement — 30RA042-055LEGENDC — Contactor, CompressorCB — Circuit BreakerCHC — Cooler/Pump Heater ContactorCWP — Chilled Wate

Pagina 48

51Fig. 25 — Control and Field Power Wiring Diagram — 30RA010-030NOTES:1. Factory wiring is in accordance with UL 1995 standards. Field modificationsor

Pagina 49

52Fig. 26 — Control and Field Power Wiring Diagram — 30RA032-055NOTES:1. Factory wiring is in accordance with UL 1995 standards. Field modificationsor

Pagina 50

53Alarms and Alerts — These are warnings of abnormalor fault conditions, and may cause either one circuit or thewhole unit to shut down. They are assi

Pagina 51

54Table 29 — Alarm and Alert Codes (cont)ALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROLRESETMETHODPROBABLECAU

Pagina 52

55Table 29 — Alarm and Alert Codes (cont)ALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROLRESETMETHODPROBABLECAU

Pagina 53 - Alarms and Alerts —

56Table 29 — Alarm and Alert Codes (cont)ALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROLRESETMETHODPROBABLECAU

Pagina 54

57Table 29 — Alarm and Alert Codes (cont)LEGENDALARM/ALERTCODEALARMORALERTDESCRIPTIONWHY WAS THISALARMGENERATED?ACTION TAKENBY CONTROLRESETMETHODPROBA

Pagina 55

58SERVICEElectronic ComponentsCONTROL COMPONENTS — Unit uses an advanced elec-tronic control system that normally does not require service.For details

Pagina 56

59BASECOMPRESSORCOMP A1COMP A2COMP B1COMP B2COMP A1COMP A2Fig. 27 — Typical Compressor Mounting — All SizesFig. 28 — Compressor WiringFig. 29 — Compre

Pagina 57

6Fig. 1 — Typical Control Box for 30RA010-030 (022-030 Shown)

Pagina 58 - Electronic Components

60Check Oil Charge — Compressors are factory chargedwith oil as shown in Table 31.Table 31 — Oil ChargeIf oil is visible in the compressor sight glass

Pagina 59 - Fig. 28 — Compressor Wiring

61• Thoroughly rinse all surfaces with low velocity cleanwater using downward rinsing motion of water spraynozzle. Protect fins from damage from the s

Pagina 60 - Condenser Section and Coils

62The amount of capacity reduction achieved by the mini-mum load valve is not adjustable. The total unit capacity withthe minimum load valve is shown

Pagina 61

63COOLER FREEZE-UP PROTECTIONThe Main Base Board (MBB) monitors leaving fluid tem-perature at all times. The MBB will rapidly remove stages ofcapacity

Pagina 62 - LOCATION

64Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop(Voltage Drop for Entering, Leaving Water and Outside-Air Thermistors T1, T2,

Pagina 63 - Flow Sensor —

65Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop(Voltage Drop for Entering, Leaving Water and Outside-Air Thermistors T1, T2,

Pagina 64

66Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop(For Thermistor T10)TEMP(F)VOLTAGEDROP(V)RESISTANCE(Ohms)–254.758 196,453–244.

Pagina 65

67Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop(For Thermistor T10)TEMP(C)VOLTAGEDROP(V)RESISTANCE(Ohms)–324.762 200,510–314.

Pagina 66 - (For Thermistor T10)

68Strainer — Periodic factory-installed strainer cleaning isrequired. Pressure drop across strainer in excess of 3 psi(21 kPa) indicates the need for

Pagina 67

69PROGRAMMINGMotormaster V control is completely configured according tothe inputs provided. No additional programming is necessary.The drive can disp

Pagina 68 - Motormaster® V Controller —

7Fig. 2 — Typical Control Box for 30RA032-055 (042-055 Shown)

Pagina 69

70L1L2L3ModeDANGERT1T2T3B+B-DISPLAYBUTTONSModeMMVTERMINALBLOCK125611122 14 13A 13B 13C 15 25 2 30 31 TXATXBCOM+5VMMVTERMINALBLOCKFig. 38 — Pressure Tr

Pagina 70

71Table 37 — Fault CodesManual Reset — If fault condition has been removed, cyclepower to the chiller to reset the VFD.Troubleshooting — Troubleshooti

Pagina 71

72Table 38 — Motormaster® V Program Parameters for Operating Modes LEGENDPARAMETERS DESCRIPTIONMODE 1MODE 2MODE 3MODE 4P01Line Vo

Pagina 72

73REPLACING DEFECTIVE MODULES — The Comfort-Link™ replacement modules are shown in Table 39. If the MainBase Board (MBB) has been replaced, verify th

Pagina 73 - Hydronic Package —

74MAINTENANCERecommended Maintenance Schedule — The fol-lowing are only recommended guidelines. Jobsite conditionsmay dictate that maintenance schedul

Pagina 74 - Actual Start-Up —

755. Allow unit to operate and confirm that everything is func-tioning properly. Check to see that leaving fluid tempera-ture agrees with leaving set

Pagina 75 - SIGHT GLASS

76Table 41 — Temperature Limits forStandard 30RA UnitsLEGEND*For sustained operation, EWT should not exceed 85 F (29.4 C).†Unit requires modification

Pagina 76 - OPERATION SEQUENCE

77APPENDIX ACCN TablesA_UNIT (General Unit Parameters)CIRCADIO (Circuit A Discrete Inputs/Outputs)CIRCA_AN (Circuit A Analog Parameters)DESCRIPTION VA

Pagina 77 - APPENDIX A

78CIRCBDIO (Circuit B Discrete Inputs/Outputs)CIRCB_AN (Circuit B Analog Parameters)OPTIONS (Unit Parameters)DESCRIPTION VALUE UNITS POINT NAME FORCEA

Pagina 78 - OPTIONS (Unit Parameters)

79ALARMDEF (Alarm Definition Table)BRODEFS (Broadcast POC Definition Table)DISPLAY (Marquee Display SETUP)DUALCHIL (Dual Chiller Configuration Setting

Pagina 79

8Fig. 3 — Wiring Schematic 30RA010-01830RA010-018 AQUA SNAP

Pagina 80

80OPTIONS1 (Options 1 Configuration)OPTIONS2 (Options 2 Configuration)DESCRIPTION VALUE DEFAULT UNITS POINT NAMECooler Fluid 1 = Water2 = Med. Brine1F

Pagina 81 - SETPOINT

81RESETCON (Temperature Reset and Demand Limit)SCHEDOVR (Timed Override Setup)SETPOINTDESCRIPTION VALUE DEFAULT UNITS POINT NAMECOOLING RESETCooling R

Pagina 82

82UNITMAINTENANCEALARMS: Maintenance DisplayDESCRIPTION VALUE DEFAULT UNITS POINT NAMECompressor A1 Size 8 to 1560 Hz: 010-10; 015-15; 018-9; 022-9; 0

Pagina 83 - DUALCHIL: Maintenance Display

83CURRMODS: Maintenance DisplayDUALCHIL: Maintenance DisplayDESCRIPTION VALUE POINT NAMEFSM controlling Chiller On/Off MODE_1WSM controlling Chiller O

Pagina 84 - LOADFACT: Maintenance Display

84LEARNFNS: Maintenance DisplayLOADFACT: Maintenance DisplayOCCUPANCY SUPERVISORY (OCCDEFM): Maintenance DisplayDESCRIPTION VALUE UNITS POINT NAMEFan

Pagina 85 - PM-STRN: Maintenance Display

85PM-COIL: Maintenance DisplayPM-PUMP: Maintenance DisplayPM-STRN: Maintenance DisplayDESCRIPTION VALUE UNITS POINT NAMECoil Cleaning Srvc Inter nnnnn

Pagina 86 - RUNTEST: Maintenance Display

86RUNTEST: Maintenance DisplayDESCRIPTION VALUE UNITS POINT NAMEPercent Total Capacity nnn % CAPA_TPercent Available Cap. nnn % CAPA_ADischarge Pressu

Pagina 87 - VERSIONS: Maintenance Display

87STRTHOUR: Maintenance DisplayTESTMODE: Maintenance DisplayVERSIONS: Maintenance DisplayDESCRIPTION VALUE UNITS POINT NAMEMachine Operating Hours nnn

Pagina 88 - WSMDEFME: Maintenance Display

88WSMDEFME: Maintenance DisplayDESCRIPTION VALUE UNITS POINT NAMEWSM Active? Yes WSMSTATChilled water temp snn.n°F CHWTEMPEquipment status On CHLRSTCo

Pagina 89 - APPENDIX B

89APPENDIX BFACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP,AND MANUAL STARTERSUNITSIZE30RAVOLTAGEV-PH- H zVOLTAGE SERIESOVERLOAD RELAY (CA1) SETTING FORCO

Pagina 90 - AND MANUAL STARTERS (cont)

9SEE NOTE 8SEE NOTE 8Fig. 3 — Wiring Schematic 30RA010-018 (cont)AQUA-SNAP LOW VOLTAGE CONTROL SCHEMATIC (010-018)

Pagina 91 - CCN TABLE

90FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP,AND MANUAL STARTERS (cont)UNITSIZE30RAVOLTAGEV-PH- H zVOLTAGESERIESOVERLOAD RELAY (CA1) SETTING FOR COMPR

Pagina 92

91APPENDIX CBuilding Interface — The 30RAN chiller can be inter-faced with multi-vendor control systems through 3 levels ofinter-operability using BAC

Pagina 93 - I. Project Information

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Pagina 94 - III. Unit Start-Up

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 9

Pagina 95

CL-25. CHILLED WATER PUMP STARTER INTERLOCKED WITH CHILLER.YES NO6. CHILLED WATER FLOW SWITCH IS OPERATIONAL.YES NO7. WATER LOOP VOLUME GREATER THAN M

Pagina 96 - MODE — RUN STATUS

CL-3OPERATING DATA:RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHENMACHINE IS IN A STABLE OPERATING CONDITION:PRESSURE/

Pagina 97

CL-4Record Software VersionsMODE — RUN STATUS(PRESS ENTER & ESCAPE SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS)COMMENTS:___________________________

Pagina 98

CL-5III. Unit Start-Up (cont)RECORD CONFIGURATION SETTINGSUNIT (Configuration Settings)PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DIS

Pagina 99

CL-6III. Unit Start-Up (cont)PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’.PRESS ENTER KEY.RECORD CONFIGURATION INFORMATI

Pagina 100 - III. Unit Start-Up (cont)

CL-7III. Unit Start-Up (cont)PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’.PRESS ENTER KEY.RECORD CONFIGURATION INFORMATI