CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB________ V AC________ V BC ________ V
(AB + AC + BC)/3 = AVERAGE VOLTAGE = _________ V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = _________V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = _________ %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. Start-Up
CHECK INDOOR (EVAPORATOR) FAN SPEED AND RECORD. ___________
CHECK OUTDOOR (CONDENSER) FAN SPEED AND RECORD. _____________
AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE (38AKS only) ___________
SUCTION PRESSURE ___________ Psig (kPa)
SUCTION LINE TEMP ___________ °F (°C)
DISCHARGE PRESSURE ___________ Psig (kPa)
DISCHARGE LINE TEMP ___________ °F (°C)
ENTERING CONDENSER-AIR TEMP ___________ DB
LEAVING CONDENSER-AIR TEMP ___________ DB
EVAP ENTERING-AIR DB (dry bulb) TEMP ___________
EVAP ENTERING-AIR WB (wet bulb) TEMP ___________
EVAP LEAVING-AIR DB TEMP ___________
EVAP LEAVING-AIR WB TEMP ___________
COMPRESSOR AMPS (L1/L2/L3) ______ / ______ / _______
HAS REFRIGERANT CHARGE BEEN ADJUSTED PER CHARGING CHARGE? __________
NOTES:
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
Vista de pagina 15
1 2 ... 11 12 13 14 15 16

Comentarios a estos manuales

Sin comentarios