Installation Instruction40GVC / 38GVC40GVQ / 38GVQHigh---W all Ductless Split SystemsSize 9K --- 36KNOTE: Read the entire instruction manual before st
10Outdoor Unit WiringConnections1. Mount outdoor power disconnect.2. Run power wiring from main box to disconnect per NECand local codes. Set outdoor
11UNIT DAMAGE HAZARDFailure to follow this caution may result in equipmentdamage or improper operation.Never use the system compressor as a vacuum pum
12START--UPTest OperationPerform test operation after completing gas leak and electricalsafety check.1. Push the “ON/OFF” button on Remote Control to
13WIRING DIAGRAMSN S L L N GND N S L GNDGround Ground115-1-60 Low V DC 115-1-60 115-1-60 115-1-60 115-1-60 Low V DC 115-1-6038GV/40GV 9K~12K 115-1-6
14TROUBLESHOOTINGThis unit has on--board diagnostics. Error codes will appear on the LED display on the front panel of the indoor unit in place of the
15TROUBLESHOOTING (CONTINUED)Diagnostic Codes38/40GVC/Q 12K, 230vMalfunctionError Code on in-door unitRepair Method/CauseIndoor PCB Malfunction EE Rep
16TROUBLESHOOTING (CONTINUED)Diagnostic Codes38/40GVC/Q 18k--24k, 230vMalfunctionError Codeon indoor unitRepair Method/CauseSystem high pressure prote
17TROUBLESHOOTING (CONTINUED)Diagnostic Codes38/40GVC/Q 30k--36k, 230vMalfunctionError Codeon indoor unitRepair Method/CauseDefrosting H1 H1 signal no
18Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231Manufacturer reserves the right to change, at any time, specifications and
2SAFETY CONSIDERATIONSInstalling, starting up, and servicing air--conditioning equipmentcan be hazardous due to system pressures, electrical component
3Connecting (Power and ControlCable)Power Wiring:The main power is supplied to the outdoor unit. The field suppliedconnecting cable from the outdoor u
4DIMENSIONS -- INDOORWDHA12377Unit SizeWIn. (mm)HIn. (mm)DIn. (mm)Net Operating WeightLbs. (Kg)9K 30.3 (770) 11.1 (283) 7.9 (201) 18.7 (8.5)12K 30.3 (
5DIMENSIONS -- OUTDOOR CONTINUED25.9 (658)10.8 (274)28.0 (711)18.5 (470)12.5 (318)11.8 (300)21.7 (551)Unit: IN. (mm)Unit: IN. (mm)A12532Fig. 3 --- 12K
6DIMENSIONS -- OUTDOOR CONTINUED14.6(370.8)36(914.4)24(609.6)15.7(398.8)31.1(789.9)38.6(980.4)16.7(424.2)in. (mm)A12379Fig. 5 --- 30K and 36K (Net Ope
7CLEARANCESvalve cover The clearance dimensions are necessary for a correct installationand are the minimum permissible distances to adjacent struc
8INSTALLATION GUIDEIdeal installation locations include:IndoorUnitS A location where there are no obstacles near inlet and outlet area.S A location wh
9DRILL HOLE IN WALL FOR INTERCONNECTINGPIPING, DRAIN AND WIRINGRefrigerant Line RoutingThe refrigerant lines may be routed in any of the four directio