40QNC024 with 38HDF024
13 SEER High Wall Duct---Free Split --- Cooling Only
with Puron Refrigerant
Submittal Data
Job Data:_________________________________________________ Location:________________________________________
Buyer:________________________________________ Buyer P.O.#_______________________Carrier # _________________
Unit Number:__________________________________ Model Number: _____________________________________________
Performance Data Certified By: _________________________________________ Date: _______________________________
40QNC
38HDF
the environmentally sound refrigerant
FEATURES
S
13 SEER / 11 EER
S Remote control standard
S Optional colored front panels
S Optional wired controls
S Auto restart on power failure
S De--humidification mode
S User selectable fan speeds (Auto, low, med, high)
S System diagnostics
S Cleanable filters
S Cooling to --20F using low ambient accessories
S Limited Warranty: 1--year on all parts/5--years on
compressor
Indoor Unit -- 40QNC / Outdoor Unit -- 38HDF
(Unless otherwise indicated, data applies to both indoor and outdoor models)
SYSTEM SIZE 024...........................................
REFRIGERANT R--410A......................................
OPERATING WEIGHT(lb)
Indoor 31...............................................
Outdoor 176.............................................
PERFORMANCE
Nominal Capacity
Indoor (Btuh) 24,000.....................................
Outdoor (Tons) 2.0.......................................
SEER 13..................................................
Moisture Removal Rate(Pints/hr) 7.9............................
Airflow (Low/Med/High) 460 / 525 / 645........................
ELECTRICAL
Power Wires 10 AWG........................................
System Voltage 208/230......................................
MCA
Indoor 0.48.............................................
Outdoor 16.8............................................
MOCP
Indoor 15...............................................
Outdoor 25..............................................
Fan Motor (Indoor) (FLA) .38.................................
Motor Watts 64.............................................
CONTROLS
Control Remote (Standard) Wireless............................
Control Voltage 24v.........................................
Control Wiring (0--50 ft.) 18 AWG..............................
Control Wiring (75--200 ft.) 16 AWG............................
REFRIGERANT LINES (Insulate both lines)
Mixed Phase Line (in.) OD 3/8................................
Vapor Line (in.) OD 5/8.....................................
Metering/Control Device Accurater Piston at outdoor unit..........
Condensate Pump: Standard j Accessory j Not Required j
Crankcase Heater: Standard j Accessory j Not Required j
Isolation Relay: Standard j Accessory j Not Required j
Low Ambient Kit: Standard j Accessory j Not Required j
Remote Control
Lock Mounting Kit: Standard j Accessory j Not Required j
Room Control Wiring Kit
(Multiple Units): Standard j Accessory j Not Required j
Stacking Kit: Standard j Accessory j Not Required j
Wind Baffle: Standard j Accessory j Not Required j
Winter Start Kit: Standard j Accessory j Not Required j
Wired Room
Control (One Unit): Standard j Accessory j Not Required j
Zone Mana ger: Standard j Accessory j Not Required j
Zone Manager Wiring Kit: Standard j Accessory j Not Required j
Comentarios a estos manuales