Performance Summary For FC- 89 93 94 97 98
Project: LAKELAND COLLEGE NE HALL 02/12/2013
Prepared By: 07:59AM
Unit Parameters
Tag Name:
FC- 89 93 94 97 98
Quantity:
7
Unit Model:
42VEA02ALCY5AYYY
Unit Type:
42VE Vertical, Lo-Boy, Cabinet
Unit Size:
200 CFM
System Type:
2-Pipe Heating and Cooling
Cooling Coil:
Cold Fluid Cooling
Cooling Coil Rows:
2 rows
Heating Coil:
Hot Fluid Heating
Coil Hand:
Left Hand
Coil Wrapping:
None
Shipping Options:
Standard
Fan Speed:
Low
Motor/Drive:
Standard
Unit Performance
Actual Airflow:
125.0
CFM
Altitude:
0
ft
External Static Pressure:
.00
in wg
Voltage:
120-1-60
V-Ph-Hz
Cooling Data
Coil Type:
Cold Fluid Cooling
Coil Rows:
2 rows
Fluid Type:
Fresh Water
Total Capacity:
3,653
BTU/hr
Sensible Capacity:
2,386
BTU/hr
Entering Air Dry Bulb Temperature:
75.0
F
Entering Air Wet Bulb Temperature:
63.0
F
Leaving Air Dry Bulb Temperature:
57.5
F
Leaving Air Wet Bulb Temperature:
52.9
F
Fluid Flow Rate:
1.3
gpm
Fluid Pressure Drop:
2.87
ft wg
Fluid Entering Temperature:
42.0
F
Fluid Leaving Temperature:
47.6
F
Heating Data
Coil Type:
Hot Fluid Heating
Fluid Type:
Fresh Water
Sensible Capacity:
7,945
BTU/hr
Entering Air Temperature:
60.0
F
Leaving Air Temperature:
118.1
F
Fluid Flow Rate:
1.3
gpm
Fluid Entering Temperature:
180.0
F
Fluid Leaving Temperature:
167.8
F
Fluid Pressure Drop:
2.14
ft wg
Electrical Data
Motor Voltage:
120-1-60
V-Ph-Hz
Motor FLA (per motor):
0.6
Acoustical Data:
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA
Sound Power Data
Radiated Sound Power, dB 50 48 43 38 33 29 NA 45
Discharge Sound Power, dB NA NA NA NA NA NA NA NA
Factory-Installed Options
Unit Arrangement:
Front Return / Top Supply
Filters:
Std 1 in. Throwaway
Drain Pans:
Standard Drain Pan
Coil Hand:
Left Hand
AAV / Drains:
Manual Air Vents only
Control Packages:
Line Voltage Tstat by Others
Insulation:
Std. Tufskin II Insulation
Fan Coil Builder 4.04 Page 5 of 5