AIR THROW DATA
Model Number
Approximate Air Throw ft. (m)
Low Medium High Turbo
4 0 G V M 0 0 9 --- --- --- 3 18 (5.5) 21 (6.4) 24 (7.3) 27 (8.2)
4 0 G V M 0 1 2 --- --- --- 3 19 (5.8) 21 (6.4) 24 (7.3) 27 (8.2)
4 0 G V M 0 1 8 --- --- --- 3 25 (7.6) 29 (8.8) 32 (9.8) 35 (10.7)
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBA Sound Pressure dBA
3 8 G V M 2 1 8 --- --- --- 3 ( c o o l / h e a t ) 66/66 56/56
3 8 G V M 3 2 4 --- --- --- 3 ( c o o l / h e a t ) 66/66 56/56
3 8 G V M 4 3 0 --- --- --- 3 ( c o o l / h e a t ) 66/66 56/56
3 8 G V M 4 3 6 --- --- --- 3 ( c o o l / h e a t ) 69/69 59/59
3 8 G V M 5 4 2 --- --- --- 3 ( c o o l / h e a t ) 68/68 58/58
Indoor Units
Model Number
Low Medium High Turbo
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
4 0 G V M 0 0 9 --- --- --- 3 36.0 26.0 45.0 35.0 47.0 37.0 51.0 41.0
4 0 G V M 0 1 2 --- --- --- 3 38.0 28.0 46.0 36.0 48.0 38.0 52.0 42.0
4 0 G V M 0 1 8 --- --- --- 3 45.0 35.0 50.0 40.0 54.0 44.0 56.0 46.0
NOTES:
1. Sound power ratings are per AHRI 270 and AHRI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
ELECTRICAL DATA
Outdoor Units
Unit Size
System Voltage Operating Voltage* Compressor Outdoor Fan
MCA
MAX
FUSE/CB
Amp
V O L T --- P H --- H Z MAX/MIN RLA LRA FLA HP W
18 K
208/230---1---60 253/187
9.6 27 0.54
1/12 60
13 20
24 K 14.7 45
0.59
20 30
30 K 19.6 45 26 45
36 K 21.0 45 0.67 1/8 120 28 45
42 K 21.5 67 1.10 1/6 140 29 50
Indoor Units
Unit Size
System Voltage Operating Voltage Indoor Fan{
V O L T --- P H --- H Z MAX/MIN FLA W
9K
208/230---1---60 253/187
0.20
2012 K
18 K 0.32
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ Indoor fan powered f rom outdoor u nit.
LEGEND
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA --- RatedLoadAmps
38/40GVM