Table 4 – Natural Gas Orifice Sizes and Manifold Pressure
208/230VAC Models
Nameplate
Input,
High Stage
(Btu/hr)
ALTITUDE OF INSTALLATION (FT. [m] ABOVE SEA LEVEL) U.S.A.*
0 to 2000
[0 to 610]
2001 to
3000*
[610 to 914]
3001 to 4000
[915 to 1219]
4001 to 5000
[1220 to 1524]
5001 to 6000
[1524 to 1829]
40000
Orifice No. (Qty) 44 (2) 45 (2)† 48 (2)† 48 (2)† 48 (2)†
Manifold Press. High / Low (in. W.C.) 3.2 /1.4 3.2 /1.4 3.8 /1.6 3.5 /1.5 3.2 /1.4
60000
Orifice No. (Qty) 44 (3) 45 (3)† 48 (3)† 48 (3)† 48 (3)†
Manifold Press. High / Low (in. W.C.) 3.2 /1.4 3.2 /1.4 3.8 /1.6 3.5 /1.5 3.2 /1.4
90000
Orifice No. (Qty) 38 (3) 41 (3)† 41 (3)† 42 (3)† 42 (3)†
Manifold Press. High / Low (in. W.C.) 3.6 /1.6 3.8 /1.6 3.4 /1.5 3.4 /1.5 3.2 /1.4
115000
Orifice No. (Qty) 33 (3) 36 (3)† 36 (3)† 36 (3)† 38 (3)†
Manifold Press. High / Low (in. W.C.) 3.8 /1.7 3.8 /1.7 3.6 /1.6 3.3 /1.4 3.6 /1.5
130000
Orifice No. (Qty) 31 (3) 31 (3) 33 (3)† 33 (3)† 34 (3)†
Manifold Press. High / Low (in. W.C.) 3.8 /1.7 3.2 /1.4 3.7 /1.6 3.4 /1.4 3.3 /1.4
*In the U.S.A., the input rating for altitudes above 2000 ft (610m) must be reduced by 4% for each 1000 ft (305 m) above sea level.
In Canada, the input rating for altitudes from 2001 to 4500 ft (611 to 1372 m) above sea level must be derated by 10% by an authorized gas conversion stationor
dealer.
For Canadian Installations from 2000 to 4500 ft, use U.S.A. column 2001 to 3000 ft (610 to 914 m).
† Orifices available through your distributor.
NOTE: Orifice sizes and manifold pressure settings are based on natural gas with a heating value of 1025 Btu/ft
3
and a specific gravity of .6.
Table 5 – Heating Inputs 208/230 VAC Models
HEATING INPUT
(BTUH)
GAS SUPPLY PRESSURE (IN. W.C.)
MANIFOLD PRESSURE
NUMBER OF
Natural{ Propane*{
(IN. W.C.)
Min Max Min Max Natural{ Propane*†
40,000 2 4.0 13.0 11.0 13.0 3.23.8 10.0
60,000 2 4.0 13.0 11.0 13.0 3.23.8 10.0
90,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0
115,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0
130,000 3 4.0 13.0 11.0 13.0 3.23.8 10.0
*When a unit is converted to propane, different size orifices must be used. See separate, natural ---to ---propane conversion kit instructions.
{Based on altitudes from sea level to 2000 ft (610 m) above sea l evel. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each addi-
tional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.
48VR-- A