Note to Installer: After installation, leave these instructions, Owner’s Manual and Parts
Replacement Guide with equipment owner.
CONTENTS
SAFETY CONSIDERATIONS
...........................
GENERAL .........................................................
INSTALLATION.................................................
Step 1 — Rig and Place Unit
...........................
ROOFTOP INSTALLATION
GROUND LEVEL INSTALLATION
CLEARANCES
CONDENSATE DISPOSAL
VENTING
Step 2 — Make Gas Piping Connections
Step 3 — Make Duct Connections
..................
Step 4 — Make Wiring Connections ...
HIGH-VOLTAGE CONNECTIONS
SPECIAL PROCEDURES FOR
208-V OPERATION
LOW-VOLTAGE CONNECTIONS
HEAT ANTICIPATOR SETTING
START-UP
.........................................................
SERVICE............................................................
TROUBLESHOOTING CHARTS
......................
SAFETY CONSIDERATIONS
Page
. 1
. 1,2
. 2-9
. 2
5
6
7
9-18
18-21
22,23
NOTE: Installation of this unit must conform to the
guidelines presented in these Installation Instruc
tions. Read and beeome familiar with this publica
tion before starting installation.
Only trained, qualified installers and service
mechanics should install, start-up and service this
equipment. Consult the Owner’s Manual for routine
maintenance. All other operations should be per
formed by trained service personnel.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling, rigging and setting bulky
equipment.
Observe precautions in these instructions and on
equipment tags, stickers and labels.
Fig. 1 — Model 48KHA.KLA
GENERAL
Models 48KHA,KLA packaged gas/ electric units
(Fig. 1) are design certified in accordance with
ANSI Z21.47-1983, ARI Standard 210-81 and ARl
Standard 270-84. The units are design certified by
the American Gas Association (AGA) for use with
natural or propane gases with appropriate eontrols
and orifices. See Table 1 for heating input ratings.
Models 48KHA,KLA units are fully self-contained,
combination gas-heating/electric-cooling units
designed for outdoor installation on either a rooftop
or ground-level slab.
These units are equipped with an energy-saving
automatic, intermittent, electric spark ignition
system that does not have a continuously burning
pilot. All units are manufactured with natural gas
controls.
© Carrier Corporation 1984
Form 48KH,KL-9SI
Vista de pagina 0
1 2 3 4 5 6 ... 23 24

Indice de contenidos

Pagina 1 - 1 — Rig and Place Unit

HCarrier Corporation • Syracuse. N Y 13221Packaged Heating/Cooling UnitsNote to Installer: After installation, leave these instructions, Owner’s Manua

Pagina 2 - Rig and Place Unit

d. Make sure condensate drain pan is filled with water to ensure proper drainage.e. Make sure all tools and miscellaneous loose parts have been remo

Pagina 3 - TO DRAIN

6. Multiply result of step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value with heating input shown

Pagina 4 - Weight Data

2. Open air shutter very slowly until yellow tip just disappears, then secure air shutter in place with locking screw.3. Repeat steps 1 and 2

Pagina 5

C — ContactorCap. — CapacitorComp — CompressorGV — Gas ValveIFM — Indoor Fan MotorIFMC — Indoor Fan Motor CapacitorIFR “ Indoor Fan Relay (Cooling)I

Pagina 6 - (Sq In.)*

Table 6 — Model 48KHA.KLA Air Delivery (cfm)*at Indicated External Static Pressure and VoltageMODEL48-UNIT VOLTS- PHASE (60 Hz)BLOWERMOTORSPEEDCOlLtEX

Pagina 7

Table 6 — Model 48KHA,KLA Air Delivery (cfm)*at Indicated External Static Pressure and Voltage (cont)MODEL48*UNITBLOWEREXTERNAL STATIC PRESSURE (in wg

Pagina 8 -

CHECKING AND ADJUSTING REFRIGERANT CHARGE — Refrigerant system is fully charged with R-22 refrigerant, tested and factory sealed. For

Pagina 9 - Unit Preparation

INDOOR AIRFLOW AND ADJUSTMENTSTable 8 — Rated Cooling and Heating AirflowsModels 48KHA,KLA end-discharge units have direct-drive blower motors.

Pagina 10

CONTROLS — All compressors have the following internal-protection controls:High-Pressure Relief Valve — This valve opens when pressure differe

Pagina 11

Top RemovalAir FilterNOTE: When performing maintenance or service procedures that require removal of unit top, be sure to perform all ro

Pagina 12 - Rise and Rated Keating Input

Table 1 — Perferjpiance DataMODEL 48-COOLINGCAPACITY(Btuh)*RATEDHEATINGINPUT(Btuh)OUTPUTCAPACITY(Btuh)ARItSOUNDRATING(Bels)KLA118310BE17,80040,00032,0

Pagina 13

3. Remove and clean blower wheel.a. Ensure proper reassembly by marking wheel orientation and cutoff plate location.b. Remove screws holding

Pagina 14

Remove control, blower and compressor eom- partment access panels to locate all electrical controls and wiring. Check all electrical conn

Pagina 15

TROUBLESHOOTING CHARTTable 9 — Heating Service Analysis ChartSYMPTOMPROBABLE CAUSEREMEDYPilot will not lightNo spark at electrodeCheck air gap between

Pagina 16

TROUBLESHOOTING CHARTTable 10 — Cooling Service Analysis Chart"1SYMPTOMPROBABLE CAUSEREMEDYCompressor and con- denser fan will not startPower fai

Pagina 17

For replacement items use Carrier Specified PartsManufacturer reserves the right to discontinue, or change at any time, specifications or designs with

Pagina 18

ROOFTOP INSTALLATIONlàWhen installing a Model 48KHA,KLA end discharge unit with a field-supplied downflow plenum, a field-supplied roof-mount

Pagina 19

PLUGGED ACCESS HOLE ” FOR REFRIGERANT j!lH PRESSURE GAGE HOSES# MPTdrain conn*NOTON MODELS48KLAII8 THROUGH 136¡ KHA024 THROUGH 030.MODEL 48-KLA11

Pagina 20

Step 2 — Make Gas Piping Connections — Amanual shutoff valve is shipped loose in the burner compartment or blower compartment. Connect one

Pagina 21

Fig. 7 — Sediment Trap5. Install an accessible, external, manual shutoff valve in gas supply pipe within 6 ft of heating section.NOTE:

Pagina 22 - TROUBLESHOOTING CHART

3. Install external, field-supplied air filter(s) in return-air ductwork where it is easily accessible for service. Recommended filter

Pagina 23

Table 3 — Electrical Data (60 Hz)MODEL48-SERIESVOLTS-PHASEOPERATINGVOLTAGE*COMPR FLAMCAtMAXAMPSMAX FUSE SIZE (Amps)tMIN WIRE SIZE (AWG)tMAXWIREMinMaxR

Pagina 24 - Catalog No 534-848

IUsing cover removed from red lead, insulate loose terminal on orange lead. Wrap cover with electrical tape so that metal terminal cannot be seen.