Carrier 19XL Especificaciones Pagina 286

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 392
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 285
* [LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the
operator as an override or an alert.
Table 10D — Prestart Alerts: These alerts only delay start-up. When alert is corrected,
the start-up will continue. No reset is necessary.
Primary Message Secondary Message
Alarm Message/Primary
Cause
Additional Cause/
Remedy
Prestart Alert
Starts Limit Exceeded STARTS EXCESSIVE Com-
pressor Starts (8 in 12 hours)
Depress the RESET softkey
if additional start is required.
Reassess start-up require-
ments.
Prestart Alert
High Motor Tempera-
ture
MTRW VALUE exceeded limit
of [LIMIT]*. Check motor tem-
perature.
Check motor cooling line for
proper operation. Check for
excessive starts within a short
time span.
Prestart Alert
High Bearing Tempera-
ture
MTRB VALUE exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.
Check oil heater for proper
operation, check for low oil
level, partially closed oil sup-
ply valves, etc. Check sensor
accuracy.
Prestart Alert
High Discharge Temp CMPD VALUE exceeded limit of
[LIMIT]*. Check discharge tem-
perature.
Check sensor accuracy. Allow
discharge temperature to
cool. Check for excessive
starts.
Prestart Alert
Low Refrigerant Temp ERT VALUE exceeded limit of
[LIMIT]*. Check refrigerant tem-
perature.
Check transducer accuracy.
Check for low chilled water/
brine supply temperature.
Prestart Alert
Low Oil Temperature OILT VALUE exceeded limit of
[LIMIT]*. Check oil temperature.
Check oil heater power, oil
heater relay. Check oil level.
Prestart Alert
Low Line Voltage V
P VALUE exceeded limit of
[LIMIT]*. Check voltage supply.
Check voltage supply. Check
voltage transformers. Consult
power utility if voltage is low.
Adjust voltage potentiometer
in starter for SMM voltage
input.
Prestart Alert
High Line Voltage V
P VALUE exceeded limit of
[LIMIT]*. Check voltage supply.
Check voltage supply. Check
voltage transformers. Consult
power utility if voltage is low.
Adjust voltage potentiometer
in starter for SMM voltage
input.
Prestart Alert
High Condenser Pres-
sure
CRP VALUE exceeded limit of
[LIMIT]*. Check condenser
water and transducer.
Check for high condenser
water temperature. Check
transducer accuracy.
Vista de pagina 285
1 2 ... 281 282 283 284 285 286 287 288 289 290 291 ... 391 392

Comentarios a estos manuales

Sin comentarios