24APA
Performancet Series Air Conditioner
with Puronr Refrigerant
1---1/2 to 5 Nominal Tons (Size 18 To 60)
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes a nd
National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety --alert symbol
!
!
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WAR N IN G sig n ifies hazards w h ich cou ld resu lt in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury
or equipment damage.
PuronR refrigerant systems operate at higher pressures than
standard R -- 22 systems. Do not use R--22 service
equipment or components on Puron refrigerant equipment.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity .
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb
vibration.
5. When passing refrigerant tubes through the wall, seal
opening with RTV or other pliable silicon--based caulk.
(See Fig. 1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely
surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4
mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
INSULATION
VAPOR TUBE
LIQUID TUBE
OUTDOOR WALL INDOOR WALL
LIQUID TUBE
VAPOR TUBE
INSULATION
CAULK
Avoid contact between tubing and structureNOTE:
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
JOIST
1 (25.4 mm)MIN.
SUSPENSION
A94028
Fig. 1 -- Connecting Tube Installation
Vista de pagina 0
1 2 3 4 5 6 ... 11 12

Indice de contenidos

Pagina 1 - Installation Instructions

24APAPerformancet Series Air Conditionerwith Puronr Refrigerant1---1/2 to 5 Nominal Tons (Size 18 To 60)Installation InstructionsNOTE: Read the entire

Pagina 2 - INSTALLATION

1001020304050607080900 (-17.77)20 (-6.67)40 (4.44)60 (15.56)80 (26.67)100 (37.78)120 (48.89)TEMPERATURE °F (°C)RESISTANCE (KOHMS)THERMISTOR CURVEA0805

Pagina 3 - ISO 9001:2000

11A06305LEGEND24--V FACTORY WIRING24--V FIELD WIRINGFIELD SPLICE CONNECTIONA97368Fig. 12 -- Non--Communicating Standard Thermostat 3--Wir e 24V Circui

Pagina 4 - Make Electrical Connections

12FINAL CHECKSIMPORTANT: Before leaving job, be sure to do the following:1. Ensure that all wiring is routed away from tubing and sheetmetal edges to

Pagina 5 - CompressorCrankcaseHeater

2Outdoor unit contains system refrigerant charge for operation withARI rated indoor unit when connected by 15 ft. (4.57 m) offield -- sup plied o r fa

Pagina 6 - Check Charge

3Outdoor units may be connected to indoor section using accessorytubing package or field -- supplied refrigerant grade tubing of correctsize and condi

Pagina 7 - UTILITY RELAY

4Install Liquid Line Filter Drier IndoorCAUTION!UNIT DAMAGE HAZARDFailure to follow this caution may result in equipment damageor improper operation.I

Pagina 8 - TROUBLESHOOTING

5!WARNINGELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury or death.The unit cabinet must have an uninterrupted or

Pagina 9 - STATUS CODES

6Start--UpCAUTION!UNIT OPERATION AND SAFETY HAZARDFailure to follow this caution may result in minor personalinjury, equipment damage or improper oper

Pagina 10 - THERMISTOR CURVE

7GENERAL SEQUENCE OF OPERATIONSTANDARD THERMOSTATTurn on power to indoor and outdoor units. Transformer isenergized.On a call for cooling, thermostat

Pagina 11 - Specific Unit combinations)

8for the remainder of the cooling cycle. If the LPS does not closewithin 10 minutes, then the normal LPS trip response (shutdown cooling operation and

Pagina 12 - CARE AND MAINTENANCE

9STATUS CODESTable 3 shows the status codes flashed by the amber status light.Most system problems can be diagnosed by reading the status codeas flash