Outdoor unit contains system refrigerant charge for operation with
ARI rated indoor unit when connected by 15 ft. (4.57 m) of
field -- sup plied o r facto ry accesso ry tu bin g. Fo r pro per u nit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of
this instruction.
IMPORTANT: Maximum liquid--line size is 3/8--in. OD for all
residential applications including long line.
IMPORTANT: Always install the factory--supplied liquid--line
filter drier. Obtain replacement filter driers from your distributor or
branch.
INSTALLATION
Specifications for this unit in residential new construction market
require the outdoor unit, indoor unit, refrigerant tubing sets,
metering device, and filter drier listed in presale literature. There
can be no deviation. Consult the Application Guideline and
Service Manual – Air Conditioners and Heat Pumps Using Puronr
Refrigerant to obtain required unit changes for specific applications
andforR--22retrofit.
Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage
unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base p an. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
For hurricane tie downs -- contact your local distributor for details
and PE (Professional Certification), if required by local authorities.
On rooftop applications, mount on level platform or frame. Place
unit above a load--bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles.
Consult the Application Guideline and Service Manual --
Residential Split System Air Conditioners and Heat Pumps Using
Puronr Refrigerant for wind baffle construction.
NOTE: Unit must be level to within ±2_ (±3/8 in./ft..) per
compressor manufacturer specifications.
Clearance Requirements
Wh en in stallin g, allow su fficient space fo r airflow clearan ce,
wiring, refrigerant piping, and service. Allow 30 in. (762 mm)
clearance to service end of unit and 48 in. (1219.2 mm) above unit.
For proper airflow, a 6 in. (152.4 mm) clearance on one side of
unit and 12 in. (304.8 mm) on all remaining sides must be
maintained. Maintain a distance of 24 in. (609.6 mm) between
units. Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
VIEW
FROM TOP
3/8--IN. DIA. TIEDOWN KNOCKOUTS
IN BASEPAN (2) PLACES
UNIT BASE
PAN
DIMENSIONS
in. (mm)
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
A B C
29--- 1/2 X 33
(749.3) X (838.2)
10–1/16
(255.6)
5–5/8
(142.9)
23–3/4
(603.3)
36–1/2 X 40
(927.1)
9–5/8
(244.5)
6–13/16
(173.0)
28–3/4
(730.3)
A05177
Fig. 2 -- Tiedown Knockout Locations
On rooftop applications, locate unit at least 6 in. (152.4 mm) above
roof surface.
Operating Ambient
The minimum outdoor operating ambient in cooling mode is 55°F
(12.78 _C) without low ambient cooling enabled, and the
maximum outdoor operating ambient in cooling mode is 125°F
(51.67_C).
Make Piping Connections
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal injury
or death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Use all service ports and open all flow--control devices,
including solenoid valves.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not leave system open to atmosphere any longer than
minimum required for installation. POE oil in compressor is
extremely susceptible to moisture absorption. Always keep
ends of tubing sealed during installation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4
mm) vertical rise at service valve. Refrigerant tubing lengths
up to 36 in. (914.4 mm) may be buried without further
special consideration. Do not bury lines more than 36 in.
(914.4 mm).