42VMC---N
GB - 17
ENGLISH
Units are prearranged for introduction of renewal air through
a prepunched hole located on back side.
Back knockout allows connection of fresh air inlet duct.
Use locally purchased material, suitable for operating
temperatures of 60 °C (continuous).
Conduits can be of flexible polyester (with spiral core) or
corrugated aluminium, externally covered with anti-condensate
material (fibre glass from 12 to 25 mm thickness).
To complete the installation, all non-insulated ducts must be
covered with anti-condensate insulation (ex. expanded
neoprene, 6 mm thickness).
Not observing of these instructions may cause
condensate dripping; the manufacturer will not be held
responsible for any damage caused.
The supplementary fan motor for outside air intake has to be
supplied separately and controlled by a bipolar ON-OFF switch
with safety fuses (field-installed).
To adjust the fan motor air flow to the required values it is
advisable to install a speed controller.
Fresh air flow must be less than 10% of the total air flow, to
avoid operating problems.
For fresh air ventilation rates higher than 10%, a primary air
treatment system with separate deflectors is recommended.
Install an air inlet grille with filter inspection port to prevent
dust and dirt from entering and fouling the indoor unit heat
exchanger.
Filter installation also makes the installation of a duct closing
damper during shutdown periods unnecessary.
570
100
Ø 80
Models 009N - 012N
Models 014N - 018N - 024N
Hole for external air intake
Models 028N - 048N
Ø 70
Ø 74
Fresh air renewal