Actual start-up
IMPORTANT:
Commissioning and start-up of the chiller must be
supervised by a qualified refrigeration engineer.
Start-up and operating tests must be carried out with a
thermal load applied and water circulating in the
evaporator.
All set point adjustments and control tests must be carried
out before the unit is started up.
Please refer to the controls manual for the unit.
a. Start up the unit.
b. Check that all safety devices are satisfied, paticularly the
high pressure switches.
For this purpose:
- Stop the condenser fans.
- Operate the machine until the high pressure switch
trips and verify that the pressure does not exceed the
cut-out value of 2900 kPa.
- Using the control point as a reference, verify the
correct operation of the unit.
Electromechanical control
Multi-step thermostat
This consists of a series of load switches actuated by the
pressure developed inside a temperature sensing bulb, installed
in the cooler inlet.
Before replacing the bulb, half fill the well with a heat
conducting sealing compound. Replace the sensor in the well
recess. The thermostat is factory-set to control from the return
water temperature through a cooling range of 5.6 K.
The sequence switches are factory-calibrated and sealed
and should not need any field calibration. Two steps on
30GV and 30GY 020 to 035 and three steps on 30GV and
30GY 044 to 059 are available.
WARNING: Alteration of factory settings other than the design
set point, without the manufacturer's authorization, may void
the warranty.
If a different return water range or leaving water control is
specified, or if brine is to be used, the controller must be
changed. Consult your local Carrier representative for the
proper control.
Design set point adjustment (three-step thermostat)
Legend:
A - Differential between stages
B - Differential on one contact
R, Y, B - Thermostat contact reference
O - Open contact
F - Closed contact
Set point adjustment
When the unit is ready for operation, insert a small screwdriver
in the adjusting slot to turn the dial (the dial may also be turned
by hand). Rotate the screwdriver, until the design set point for
the installation appears directly under the pointer. Insert a
thermometer in the return water connection and allow the unit
to run through a complete cycle. When switch No. 1 opens, the
last capacity step appears directly under the pointer. Read the
temperature. If it is not the same as the dial reading, it can be
compensated by shifting the control point slightly.
NOTE: Do not force the dial past the stop. This could cause
loss of the control point and damage the instrument.
Set point adjustment
Control pressostats
Low pressure switch
Switches the unit off, if the evaporating temperature is too low:
Cut-out: 200 kPa
Cut-in: 350 kPa
Condensing pressure switch (2-speed option)
Energizes and de-energizes the second fan speed as a function
of the condensing pressure:
Cut-out: 1700 kPa
Cut-in: 1090 kPa
Set point
RY3
RB3
RY2
RB2
RY1
RB1
RY3
RB3
RY2
RB2
RY1
RB1
0
F
0
F
0
F
F
0
F
0
F
0
A
B
Temperature
drop
Temperature
rise
Calibrated dial
Stop
Pointer
Adjusting slot
Set points