Carrier Edge TP-PHP Manual de instrucciones

Busca en linea o descarga Manual de instrucciones para Termostatos Carrier Edge TP-PHP. Carrier Edge TP-PHP Instruction manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
T P --- P A C , T P --- P H P
T P --- N A C , T P --- N H P
Performance™ Series
AC / HP Thermostat
Installation Instructions
A07049 A07048
Programmable Control Non--Programmable Control
Designed and Assembled in the U.S.A.
NOTE: Read the entire instruction manual before starting the installation.
US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2.
Vista de pagina 0
1 2 3 4 5 6 ... 67 68

Indice de contenidos

Pagina 1 - Installation Instructions

T P --- P A C , T P --- P H PT P --- N A C , T P --- N H PPerformance™ SeriesAC / HP ThermostatInstallation InstructionsA07049 A07048Programmable Cont

Pagina 2

8Carton contains the following components. See Fig. 3 for programmable models orFig. 4 for non--programmable models.1. Display Module2. Stand--off for

Pagina 3 - SAFETY CONSIDERATIONS

9S Close to or in a frequently used room, preferably on an inside partition-ing wall.S On a section of wall without pipes or duct work.AC/HP Control s

Pagina 4 - INTRODUCTION

10UNIT DAMAGE HAZARDFailure to follow this caution may result in equipment damage orimproper operation.Improper wiring or installation may damage AC/H

Pagina 5 - INSTALLATION CONSIDERATIONS

11Two--Piece InstallationThe following steps should be followed for the installation of the two--piececonfiguration.NOTE: The 2--wire pigtail is not i

Pagina 6 - Outdoor Temperature Sensor

12A07226Fig. 6 -- Take Apart2. Route wires through large hole in mounting base. Level mounting baseagainst wall (for aesthetic value only—Display Modu

Pagina 7

13A07165Fig. 7 -- Backplate Mounting3. Drill two 3/16--in. mounting holes in wall where marked. Thermostat maybe mounted to a standard junction box, i

Pagina 8 - INSTALLATION

14 RelaysOATRRSSRTNHUMD1D2V+VgRcRhW / W1GY/Y2Y used for single stage coolingCO/W2/BY1Y1 used for multi-speed coolingY1 = stage 1Y2 = stage 2Control Mo

Pagina 9 - Fig. 2 -- Coil Excess Wiring

15A07166Fig. 9 -- Secure Wires to Terminal StripA07167Fig. 10 -- Connect Pigtail Wires to Display Module

Pagina 10 - AC/HP Control Location

16NOTE: The 2--wire pigtail is not intended to support the weight of the UserInterface. Do not hang the User Interface from the equipment Control Modu

Pagina 11 - Install AC/HP Control

1710. Find suitable indoor mounting location for Equipment Control Module, ei-ther near or on equipment. See Fig. 12.IMPORTANT NOTE: Equipment Control

Pagina 13 - Two--Piece Installation

18A07227Fig. 13 -- StandoffNOTE: Standoffs are provided as an aid when installing Equipment ControlModule on inside equipment or a solid wall.12. Matc

Pagina 14

19A07218Fig. 14 -- Cover on Equipment Control Module14. Turn on power to equipment. On power up, all display segments will lightfor 5 sec. For the nex

Pagina 15

20Single--Piece InstallationThe following steps should be followed for the installation of the single--piececonfiguration.1. Remove cover from Equipme

Pagina 16 - S Black is Vg

21A07219Fig. 15 -- Equipment Control Module5. Match and connect equipment wires to proper terminals of each connectorblock.6. Push any excess wire int

Pagina 17

22A07220Fig. 16 -- Reattach Display Module9. Turn on power to equipment. On power up, all display segments will lightfor 5 sec. For the next 5 sec a 2

Pagina 18

23be properly set by the installer. (Only those marked with an asterisk * below areavailable to the homeowner.) The homeowner configurations are descr

Pagina 19

24Option 20 — Outdoor Air Temperature Offset AdjustmentOption 21* — Keypad LockoutOption 24* — Programmable/Non--Programmable(programmable models only

Pagina 20

25WHILE IN CONFIGURATION MODEThe option number is displayed in the heat setpoint location and the configurationsetting is displayed in the cool setpoi

Pagina 21

26DefaultsHP model defaults to HP.AC model defaults to AC.Option 02 — Clean Filter TimerSelect hours of blower operation (heating, cooling, or fan) be

Pagina 22 - Single--Piece Installation

27Sensor 1Sensor 2Sensor 3Sensor 4RRSSRTNA09130Fig. 17 -- Remote Room Sensor -- Parallel WiringThis selection determines which sensor the control will

Pagina 23

1TABLE OF CONTENTSPAGESAFETY CONSIDERATIONS 1...INTRODUCTION 2...INSTALLATION CONS

Pagina 24

28Option 07 — ZoningThis selection should be set to On when the thermostat is to be used as part of azoning system. It is assumed that the zoning equi

Pagina 25

29Option 11 — Deadband Setting Between Heat & CoolThis option is not available on Heat Only and Cool Only systems. This selection isto allow the i

Pagina 26

30Option 16 — Maximum Cycles Per HourThis selection limits the number of cycles per hour that the thermostat allows thesystem to operate. Selections a

Pagina 27

31Option 19 — Dry Contact Configuration (programmable models only)There are 2 available selections, OF and 1.OF — The dry contact is always de--energi

Pagina 28

32When the keypad lock selection is turned on, the padlock icon will be displayed. Tounlock the keypad, press and hold the UP/DOWN buttons simultaneou

Pagina 29

33Option 22 — High Cool Latch Temperature (only available if outdoor sensor ispresent)An outdoor sensor is required for high cool latch feature.This s

Pagina 30

34On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all heatingdemands.Default is OF (off).Option 24 — Programmable/Non--Programmab

Pagina 31

35Option 27 — Maximum Heating SetpointThis selection allows the installer to configure the maximum heating setpoint. Therange is based on the adjustab

Pagina 32

36Option 31 — Daylight Savings Time Configuration (programmable modelsonly)This selection allows the installer to set the thermostat to automatically

Pagina 33

37Option 33 — Single or Two--Piece InstallationThis configuration allows the thermostat to compensate for the amount of heatgenerated by the thermosta

Pagina 34

2INTRODUCTIONCarrier’s 7--day, 5/2--day, 1--day programmable and non--programmablePerformance Series Thermostat Control is a wall--mounted, low--volta

Pagina 35

38If the outdoor air temperature is below 12_F/--11_C and there is sufficient demandfor the equipment to be on, then the fan output is turned back on

Pagina 36

39SYSTEM START--UP AND CHECKOUTThe AC/HP Control is designed with a built--in installer test capability. It allowseasy operation of equipment without

Pagina 37

40TO TEST FANFan button switches FAN icon between AUTO and On. While On is displayed, Goutput will be energized, turning fan on. On some fan coils, fa

Pagina 38

41The FAN button may be used to select between AUTO (fan on only withequipment) and On (fan on continuously) fan modes. For further information ontemp

Pagina 39

42Vacation SetpointsA special set of temperature setpoints exist which are active in vacation mode. Theyare adjustable by the homeowner, are exclusive

Pagina 40

43Ten--Minute Staging TimerIn multistage heating or cooling, this timer prevents any higher stage from turningon until preceding stage has been on for

Pagina 41 - SYSTEM START--UP AND CHECKOUT

44Three--Minute Minimum on TimeIn normal operation, when a stage turns on, it will not turn off for a minimum of 3minutes. If the setpoint is changed,

Pagina 42 - _C 82_F/28_C

45Programmable Fan (programmable models only)The fan output can be programmed based on period of the day. When programmingfor each day and period the

Pagina 43 - (programmable models only)

46Temperature Offset After Power CycleTo compensate for internal heat build--up from the electronics in the thermostat, thethermostat will add an offs

Pagina 44 - OPERATIONAL INFORMATION

47E3 -- If AC/HP Control cannot properly read outdoor temperature, and it is neededfor proper operation, display will indicate “----” in the outdoor t

Pagina 45

3INSTALLATION CONSIDERATIONSPowerThis control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and Cterminals) of the low--voltage transforme

Pagina 46 - Equipment On Indicators

48Table 3 – Equipment Configuration OutputsFor COOL, HEAT and Emergency Heat modes, the following chart shows the statefor each output in each stage o

Pagina 47

49Table 3 -- Equipment Configuration Outputs (cont.)EquipConfigTstatModelCOOLSTG 1COOLSTG 2HEATSTG 1HEATSTG 2HEATSTG 3HEATSTG 4EMHEATSTG 1EMHEATSTG 22

Pagina 48 - TROUBLESHOOTING

50WIRING DIAGRAMSDisplay moduleDisplay module wall mount Equipment Control ModuleFan CoilHeat PumpV+ V+Vg Vg O OV+V+ RVS/Heat Stage 2 O/B W2 W3 W2VgVg

Pagina 49

51WIRING DIAGRAMS(cont.)Thermostat Fan Coil Heat PumpOORVS/Heat Stage 2 O/B W2 W3 W2**Heat Stage 1 W/W1 W2Compressor Y/Y2 Y YNot Used Y1Fan G G24VAC H

Pagina 50

52WIRING DIAGRAMS(cont.)Thermostat Fan CoilORVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Y/Y2Not Used Y1Fan G G24VAC Hot Heating Rh R24VAC

Pagina 51

53WIRING DIAGRAMS(cont.)Thermostat Fan Coil Air ConditionerORVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Y/Y2 Y YNot Used Y1Fan G G24VAC H

Pagina 52 - WIRING DIAGRAMS

54WIRING DIAGRAMS(cont.)Thermostat Fan CoilORVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Y/Y2Not Used Y1Fan G G24VAC Hot Heating Rh R24VAC

Pagina 53 - WIRING DIAGRAMS(cont.)

55WIRING DIAGRAMS(cont.)Thermostat Furnace Air ConditionerHeat Stage 1 W/W1W/W1Compressor Y/Y2Y/Y2YNot Used Y1Fan G G24VAC Hot Heating Rh R R24VAC Hot

Pagina 54

56WIRING DIAGRAMS(cont.)ThermostatRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1Compressor Y/Y2Not Used Y1Fan G G24VAC Hot Heating Rh R24VAC Hot Cooling RcD

Pagina 55

57WIRING DIAGRAMS(cont.)Thermostat Furnace Air ConditionerW2RVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1W/W1Compressor Y/Y2Y/Y2YNot Used Y1Fan G G24VAC Ho

Pagina 56

4A07052Fig. 1 -- PCB Breakout JumperModelsThere are programmable and non--programmable models for all applications. Theycan be configured for AC or HP

Pagina 57

58WIRING DIAGRAMS(cont.)Single-Stage Single-StageThermostat Furnace Air ConditionerRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1W/W1Compressor Low Y1Compre

Pagina 58

59THERMOSTAT CONFIGURATION RECORDInstaller_________________________Model Number_____________________________Date_______________________A. Hardware Con

Pagina 59

60E Configuration OptionsOption 01_____Equipment TypeOption 02_____Clean Filter Timer AdjustmentOption 03*_____Fahrenheit/Centigrade SelectionOption 0

Pagina 60

61E Configuration Options (cont)Option 21*_____Keypad LockoutOption 22_____High Cool Latch TemperatureOption 23_____High Heat Latch TemperatureOption

Pagina 61

62NOTES

Pagina 63

64NOTES

Pagina 65

997--- 060370--- 7--- RCopyright 2013 Carrier Corporation 7310 W Morris St. Indianapolis, IN 46231T P --- P A C --- 0 7 S IR e p l a c e s : T P --- P

Pagina 66

5Remote Indoor Temperature SensorA remote temperature sensor may be used with the programmable heat pump andprogrammable air conditioner thermostats w

Pagina 67

6INSTALLATIONUNIT DAMAGE HAZARDFailure to follow the recommended wiring practices could result indamage to the wall control and personal property.Impr

Pagina 68 - T P --- P A C --- 0 7 S I

7A13295Fig. 2 -- Coil Excess WiringA07754Fig. 3 -- TP--PAC / TP--PHP Carton Contents

Comentarios a estos manuales

Sin comentarios