42PQV/38VBH
GB - 4
D
E
B
A
C
F
A
Minimum clearances and operating limits
Model 009-012
A mm 50
B mm 100
C mm 400
D mm 50
E mm 300
F mm 400
Maximum conditions
outdoor temperature 46°C
indoor temperature 32°C d.b.; 23°C w.b.
Minimum conditions
outdoor temperature 15°C
indoor temperature 21°C d.b.; 15°C w.b.
Maximum conditions
outdoor temperature 24°C d.b.; 18°C w.b.
indoor temperature 27°C d.b.
Minimum conditions outdoor temperature 10°C d.b.
Nominal single-phase voltage 220V-240V, 50/60Hz
Operating voltage limits min. 198V max. 264V
Table III: Operating limits
(1)
Cooling
Heating
Mains power supply
Obstacle
90
min.
1900
min.
100
min.
200
min.
WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures. In these cycles, fan speed will automatically stop,
louvre(flap) will be fixed at horizontal position and cannot be varied until
defrost cycle is completed.
Notes: 1. Data referred to the outdoor unit only.
d.b. - dry bulb; w.b. - wet bulb