TROUBLESHOOTING
Table 6Indicator Lamps Troubleshooting
LAMPS STATUS INDICATION CORRECTIVE ACTION
POWER flashes 10 seconds after A/C
start-up (with or without other signal lamps)
Communication problem.
Check connection between indoor
(TAC-440) and outdoor (TAC-420) units (for TAC-400, ANC).
Check connection between TAC-444 and TAC-460 (for TAC-404).
POWER, COMPRES. and PRESSURE
lamps flash.
Thermistor failure.
Check TH-1 for correct resistance.
Check for proper connection between TH-1 and TAC-444.
Replace TH-1 if necessary.
POWER, COMPRES. and IMPEDANCE
lamps flash.
Thermistor failure.
Check TH-2 for correct resistance.
Check for proper connection between TH-2 and TAC-444.
Replace TH-2 if necessary.
POWER lamp flashes and PRESSURE
is lit, AIR CON is Off.
Low Pressure
Check if the filters are clean.
Check TH-1 and TH-2 for correct resistance.
Check cooling system for normal operation.
POWER and PRESSURE lamps flash,
AIR CON is Off.
High Pressure.
In Heat mode: Check if the evaporator is blocked. (Check if filters
are clean.)
Check TH-2 (in Heating mode) or TH-3 (in Cool mode) for correct
resistance.
Check cooling system for normal operation.
FILTER is lit. Filter cleaning. Clean all filters.
POWER, IMPEDANCE lamps flash,
COMPRES. is lit.
Low voltage.
Check power supply voltage.
Check electrical connections.
Replace TAC-444.
POWER lamp flashes, IMPEDANCE
and COMPRES. lamps lit. AIR CON
lamp flashes after A/C start-up.
Voltage failure at start-up.
Check power supply voltage.
Check electrical connections.
Replace TAC-444.
POWER lamp flashes, IMPEDANCE
and COMPRES. are lit before A/C startup.
High Voltage.
Check power supply voltage.
Check electrical connections.
Replace TAC-444.
POWER lamp flashes, IMPEDANCE and
COMPRES. are lit. AIR CON is lit
after A/C startup.
High voltage during compressor operation.
Check power supply voltage.
Check electrical connections.
Replace TAC-444.