8. Remove unit from bracket and install wall plugs. After
attaching tubing and control/power wires. Remember to install
(2) hold down screws at bottom of unit.
DRILLING A HOLE IN THE WALL FOR DRAINAGE AND
INTER-UNIT CONNECTIONS
1. To make the connections between the indoor and outdoor
units, a 3-in. hole should be drilled for the refrigerant lines,
drainage hose and electric cables as shown in Fig. 9.
2. Make sure to drill outwards and downwards, so that the
opening in the outside wall is at least 1/2-in. lower than the
opening on the inside.
3. Make sure the drainage hose is at the bottom side of the hole.
(See Fig. 9.)
4. Fill the remaining wall hole gap with an appropriate sealant
material.
WIRING THE INDOOR UNIT
1. Route the inter-unit electric cable and the outdoor sensor cable
towards the lower right corner of the indoor unit.
2. Use a screw driver to insert the stripped wire ends into the
terminal block, as shown in Fig. 13.
3. Make sure that the wires are connected in accordance with the
wiring diagram on the drain pan.
4. Attach the inter-unit electric cable with the cable clamp
located on the unit.
5. Connect the Outdoor Sensor TH3 connector to its mating
connector. (See Fig. 13.)
DRAINAGE
1. Connect the unattached end of the drainage tube to the
drainage hose outlet.
2. Seal the drainage connection to prevent leakage.
3. Make sure there are no kinks, U bends or flattened sections
in the tube.
4. Check that the drainage functions properly. Fill the pan below
the units coil with water and observe that it drains out freely.
5. Connect the ends of the refrigerant lines to their appropriate
fittings, following the guidelines in the Connecting the
Refrigerant Lines section.
6. Make sure the drainage hose is at the bottom side of the wall
hole. (See Fig. 9.)
7. Connect the display panel connector to the display panel
printed circuit board. (See Fig. 13.)
8. Reassemble the front panel, using the seven screws which
appear in Fig. 5.
ATTACHING THE REMOTE CONTROLLER RACK
Use the two screws supplied to attach the remote controller rack to
the wall in the location selected by the customer. (See Fig. 12.)
CEILING INSTALLATION
IMPORTANT: When performing a ceiling installation, make sure
that Switch 1 on the Display Board is set to the ON position. (See
Fig. 11.) The remaining switches are factory set and should not be
changed.
Step 2Installing the Indoor UnitUnder Ceiling
1. The tubing connecting the indoor and outdoor units can be
routed in one of two directions, as shown in Fig. 16.
2. If the tubing is routed horizontally (direction no. 1), the pipe
cover at the bottom of the air conditioner must be removed.
(See Fig. 19.)
3. If the tubing is routed vertically (direction no. 2), a condensate
pump must be installed for drainage.
4. To assemble the ceiling bracket, use the 4 mounting strips and
the 8 UNC10 screws and nuts, as shown in Fig. 17.
5. Fasten the ceiling bracket to the ceiling using the 6 anchor
screws, as shown in Fig. 18.
6. The location of the ceiling bracket should allow a minimum
gap between the indoor unit and nearby walls, as shown in Fig.
16.
NOTE: The anchor screws provided are intended for use with
concrete ceilings.
NOTE: Use fasteners which are appropriate for the type of ceiling
present at the installation site.
Fig. 3Dimensional Drawing (Outdoor Unit)
UNIT A B C
38CG/CS-018/024
9.8-in.
(320mm)
25.2-in.
(641mm)
35.4-in.
(900mm)
38CG/CS-018/030
12.6-in.
(320mm)
25.2-in.
(641mm)
43.3-in.
(1,100mm)
A01146
0.6m(2)
min.
0.15m(6)
min.
0.15m(6)
min.
0.6m(2)
min.
c
b
a
Fig. 4Drainage Adapter Connection
A01147
5