FIELD--INSTALLED ACCESSORIES (CONT.)
OUTDOOR GRILLE SELECTION
IMPORTANT: If you wish to use a grille not made
for the Gree GA series contact Gree Application
Engineering.
The following guidelines must be followed in the
initial selection of any alternate exterior grille or
louver:
1. The louver must haveaminimum of 65% free
area. Free area is the minimum area of the
opening in an air inlet or outlet in which air can
pass. Free Area (%) = X/Y.
2. The louver should be attached to the wall sleeve
in a manner that will prevent recirculation of
condenser discharge air into the inlet. In most
applications, baffles, splitters, and/or gasket
will be required between the chassi
s tube end
sheets and the louver to prevent air
recirculation.
The above criteria must be followed, since a louver
that is restrictive or allows re--circulation will result
in a reduction of the units capacity and efficiency
and will ultimately shorten the compressor life.
X
Y
X
Y
X
Y
X
Y
Lo uver Dimensional Reference
Sample Calculations
Free Area (%) =
x
x 100
y
x = 1
y = 1.5
F.A. (%) =
1
x 100 = 66.7%
1.5
Hardwire Kit
Part No.: HARDWIRE-KIT-15A
HARDWIRE-KIT-20A
HARDWIRE-KIT-30A
This accessory hardwire kit provides a permanent
connection to the unit. Electrical hard wiring is
required when NEC (National Electrical Code) or
local codes restrict the use of power cord and plug
connections. The hardwire kit easily mounts on the
front right side of the unit and comes with 36 inches
(914.4 mm) of flexible steel conduit.
A07381
Hardwir e Kit
Conduit Interface Kit
Part No.: CONDUIT-KIT-15A
CONDUIT-KIT-20A
CONDUIT-KIT-30A
The conduit interface accessory kit provides an easy
wire connection to the unit to interface to existing
field--supplied conduit.
A07810
Conduit Interface Kit
GA
5
APPLICATION CONSIDERATIONS
Installation instructions are shipped with all PTAC
units. It is important that air conditioning systems be
properly sized and installed for each application in
ordertoachievethedesiredtemperatureandhumidity
levels within the space to be conditioned. It is
strongly recommended that a professional engineer
match thePTAC unitswiththebuilding structureand
climate.
The following application considerations are all
important in choosing the proper PTAC system for
the building structure.
Undersizing
If a PTAC unit is undersized (cooling capacity is less
than required load for an application), the unit
will not be able to cool the spac
e down to the desired
temperatureduringveryhotdays. Theresult couldbe
warm and humidor warm and dry conditionedspace.
Oversizing
If a PTAC unit is oversized (cooling capacity is
greater than required load for the specific application),
the unit will cool the space down to the desired
desired temperature too quickly.
The unit will cycle on and off, however,
dehumidification only takes place when the unit is
operating. The result of this type of application in a
hot and/or humid climate would beacool, yet
excessively humid, space.
Air Infiltration
Excessive air infiltration can intensify problems
associated with undersizing or oversizing a PTAC
unit. This can be the ca
use of insufficient cooling,
dehumidification, or heating. Sources of air
infiltration include vents, gaps around windows and
doors, and improperly sealed floors, ceilings or wall
joints.
GA
Condensate Removal
Gree’s GA series has a new condensate (water)
disposal system. The outdoor fan prop has a built in
slinger ring which draws condensate water through a
suction port built into the outdoor coil shroud. The
water passes though the suction port and is sprayed
on the warm outdoor coil for evaporation. Thus
providing better disposal of excess condensate and
improving unit operating efficiency.
It is normal and desirable to have some condensate
water in the ebase pan to boost operating efficiency.
NOTE: This unit will not always evaporate 100%
of the unit generated condensate and blown in
rain water. If it is necessary to control 100% of
the condensate, the Drain Kit (Part No.: DRAIN-
KIT-4PK) and a building condensate drain
system is recommended.