Carrier 40KMQ Especificaciones Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
10
Step 4 — Complete Refrigerant Piping
Connections
Use field-supplied refrigerant grade piping designed for use
with R-410A refrigerant.
FLARING THE ENDS OF PIPES Remove the protec-
tive caps from the copper pipe ends. Holding the tube down-
ward, cut the extreme end off, removing any copper shavings
with a deburring blade. Remove the flare nuts from the
“FLARE” connection body of the indoor unit and insert them
into the pipes. Make the flare to the pipe end with the proper
flaring tool. The flare end must not have any burrs or imperfec-
tions. The length of the flared walls must be uniform. See
Fig. 18 and 19.
Lubricate the end of pipe and the thread of the flare connec-
tion with anti-freeze oil. Tighten by hand and then use two
wrenches to tighten all connections fully, applying the tighten-
ing torque shown in Table 5. Refer to Fig. 20.
Table 5 — Tightening Torque
PIPING CONNECTION TO THE UNIT — Use two wrench-
es to tighten all connections.
Once all connections have been completed, check for leaks
using soapy water. If no leaks were found, wrap connections
with anti-condensate insulation and tighten with tape, without
exerting excessive pressure on the insulation. Repair and cover
any possible cracks in the insulation.
If either refrigerant tubing or indoor coil is exposed to
the atmosphere, the system must be evacuated following good
refrigeration practices.
IMPORTANT: During unit installation make the refrigerant
connections first and then the electrical connections. If the
unit is uninstalled, disconnect the electrical cables first and
then the refrigerant connections. Refer to the outdoor unit
installation instructions for tube sizing and limitations.
TUBE
DIAMETER
(in.)
TORQUE
(ft-lb)
3
/
8
in. 31
5
/
8
in. 48
3
/
4
in. 74
Insufficient tightening torque could cause a refrigerant leak
from the connection. Excessive tightening torque will dam-
age the pipe flare.
DO NOT BURY MORE THAN 36 IN. OF REFRIGER-
ANT PIPE IN THE GROUND. If any section of pipe is
buried, there must be a 6-in. vertical rise to the valve
connections on the outdoor unit. If more than the
recommended length is buried, refrigerant may migrate to
cooler, buried section during extended periods of system
shutdown. This causes refrigerant slugging and could
possibly damage the compressor at start-up.
L
L
Adjustable wrench or torque wrench
Outdoor end
Indoor end
3
1
2
Fig. 18 — Removing Burrs
Fig. 19 — Flared Walls are Equal
Fig. 20 — Tightening Connections
Vista de pagina 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 23 24

Comentarios a estos manuales

Sin comentarios