Step 5 — Make Electrical Connections
See Tables 6A and 6B for electrical information.
UNITS WITH ELECTRIC HEATER — The unit is equipped
with two thermostats: one with automatic reset and one with
manual (electric) reset that can be reactivated by switching the
power supply off and then back on.
POWER WIRING (Fig. 21-27) — The unit is factory wired
for voltage shown on nameplate. Provide adequate, fused dis-
connect switch within sight of unit, readily accessible, but out
of reach of children. Provision for locking the switch open
(off) is advisable to prevent power from being turned on while
unit is being serviced. Disconnect switch, fuses, and field
wiring must comply with the NEC and local code require-
ments. Use copper wire only between the disconnect
switch and unit. Use minimum 60 C wire for the field power
connection.
Remove the external box cover. Route the low voltage wires
from the outdoor unit to the indoor unit:
1. Place wiring through
7
/
8
in. knockouts on the left or right
hand side of external control box (low voltage side).
2. Connect the R and Y wires to the 2 pin terminal block for
cooling only units (40KMC) and heat pump units
(40KMQ) that are matched to 38HDF outdoor units.
3. Connect the R, Y, O, G, DT, A, and B wires to the
(PGB-1) 1 terminal for 40KMQ indoor units matched
with 38QRF outdoor units.
Route the line power leads from the indoor disconnect to the
fan coil unit.
1. Place wiring through
7
/
8
in. or 1
1
/
8
in. knockouts on the
left and on the right hand side of external control box
(high voltage side).
2. Connect L1 to the black wire and L2 to the red wire using
wire nuts and fix the ground wire between the 2 washers.
See Fig. 27 for a view of the internal control panel. The in-
ternal control panel can be accessed by opening the grille and
removing the metal cover attached by four screws.
NOTE: The internal control panel does not need to be accessed
during the installation process unless there is a need for
service.
Table 6A — 40KMC Fan Coil Electrical Data
LEGEND *Permissible limits of the voltage range at which unit will operate
satisfactorily.
NOTE: In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and 440),
the overcurrent protective device for the unit shall be fuse or
equipped with a breaker.
Table 6B — 40KMQ Fan Coil Electrical Data
LEGEND *Permissible limits of the voltage range at which unit will operate
satisfactorily.
NOTE: In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and 440),
the overcurrent protective device for the unit shall be fuse or
equipped with a breaker.
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control com-
partment, or conduit approved for electrical ground when
installed in accordance with NEC, and local electrical
codes. Failure to follow this warning could result in the
installer being liable for the personal injury of others.
Unit failure as a result of operation on improper line
voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such opera-
tion would invalidate any applicable Carrier warranty.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
40KMC
UNIT
SIZE
V-PH-Hz
VOLTAGE
RANGE*
FAN
CONDENSATE
PUMP
FLA
LOUVER
MOTOR
FLA
POWER
MIN WIRE
SIZE
AWG
Min Max FLA
Motor
Power
(Watts)
MCA MOCP
018 208/230-1-60 187 253 0.55 120 0.06 0.01 0.8 15 14
024 208/230-1-60 187 253 0.50 110 0.06 0.01 0.7 15 14
030 208/230-1-60 187 253 0.95 210 0.06 0.01 1.3 15 14
036 208/230-1-60 187 253 0.95 210 0.06 0.01 1.3 15 14
AWG — American Wire Gage
FLA — Full Load Amps
MCA — Minimum Circuit Amps per NEC Section 430-24
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
40KMQ
UNIT
SIZE
V-PH-Hz
VOLTAGE
RANGE*
FAN
CONDENSATE
PUMP
FLA
LOUVER
MOTOR
FLA
ELECTRIC
HEATERS
POWER
MIN
WIRE
SIZE
AWG
Min Max FLA
Motor
Power
(Watts)
kW FLA MCA MOCP
018 208/230-1-60 187 253 0.50 110.0 0.06 0.01 3 12.5 16.3 20 12
024 208/230-1-60 187 253 0.50 110.0 0.06 0.01 3 12.5 16.3 20 12
030 208/230-1-60 187 253 0.95 210.0 0.06 0.01 3 12.5 16.9 20 12
036 208/230-1-60 187 253 0.95 210.0 0.06 0.01 3 12.5 16.9 20 12
AWG — American Wire Gage
FLA — Full Load Amps
MCA — Minimum Circuit Amps per NEC Section 430-24
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code