23
Any of the following will cancel the Service Test mode:
When the unit is turned off by the controller.
If the power is cycled during the Test Mode, the unit will
return to its normal operating mode.
After 30 minutes of receiving the last valid test request
message.
Fail Mode.
START-UP
The following checks should be made before system start-
up. Refer to outdoor unit Installation, Start-Up, and Service
manual for system start-up instructions and refrigerant charg-
ing methods. Be sure to use the refrigerant charge shown in
Table 3.
1. Check condensate drainage system.
a. Remove grille and frame from the unit.
b. On the opposite side of the drain connection, insert
a water bottle up into the fan coil unit and fill drain
pan. Refer to Fig. 34. Water must flow regularly
with condensate pump energized. If water does
not, check the pipe slope or see if there are any
pipe restrictions.
NOTE: The unit is equipped with a safety float
switch to deenergize the compressor if the drain
water level gets too high.
2. Make sure that all wiring connections are correct and that
they are tight.
3. Make sure that all barriers, covers, and panels are in
place.
4. Ensure that the filters and return air grilles have been
installed and that the discharge louvers are correctly
positioned.
SERVICE AND MAINTENANCE
Remove unit grille, filter, and condensate pan for cleaning,
lubricating, or replacing parts.
Minimum Maintenance
1. Check, clean, or replace air filter each month or as
required.
2. Check cooling coil, drain pan, condensate trap, and con-
densate drain pan each cooling season for cleanliness.
Clean as necessary.
3. Check fan motor and wheel for cleanliness each heating
and cooling season.
4. Check electrical connections for tightness and controls
for proper operation each heating and cooling season.
Service as necessary.
Service
TO CLEAN OR REPLACE AIR FILTERS
1. Place a plastic sheet on the floor to catch any water that
may spill from drain pan.
2. Slide filter out.
3. Vacuum clean or wash filter with soapy water. Rinse and
let air dry. If filter needs replacing, filters are available
from the local dealer.
Never operate unit without a filter or with grille removed.
Damage to the unit or personal injury may result.
To avoid personal injury or damage to unit, do not service
until all power sources are shut down, locked out, and
tagged out. Failure to do so could result in personal injury
or unit damage.
If air filter is not replaced in the unit, dust and dirt gather in
air conditioner and operation becomes impaired.
Room Controller
ON
up
down
Keep it pressed
for 5 seconds
To change
the value
Automatic
(AUTO)
Or
Continuous
movement
(swing)
Fig. 33 — Selecting the Louver Mode
Fig. 34 — Inserting Water into Drain Pan