22
Louver Mode Selection — To enter louver mode
selection, ensure the room controller is on and then press the
Fan button for 5 seconds. After 5 seconds, the selected louver
setting will be displayed. Press the up and down arrows to
modify the louver setting between swing and auto. Refer to
Fig. 33. The two settings will be displayed as follows:
The fan icon will also be displayed in the louver mode.
Press Fan button to exit the Louver Mode Selection. This mode
will exit automatically after 10 seconds of inactivity. The only
way to abort a louver change is to change the value back to its
original value.
NOTE: If units are grouped to one room controller, all units
will have the same louver value. Louver Mode selection is not
available during OFF mode.
Main Board Configuration — To configure the main
electronic board, push the Up and Down arrows for 5 seconds
while the room controller is off.
After 5 seconds, a “20” will appear. This indicates that the
user is setting the first software configuration item. To check
the value of configuration item “20,” press the Mode button.
The value for the Heat Pump/AC Only configuration will be
displayed. To change the value, use the Up and Down buttons.
Once the desired value is selected, press the Fan button to send
that configuration data to the unit. Refer to Table 8.
Table 8 — Modular Platform D Unit Configuration
Values
Only the current value being displayed is transmitted. Once
the Fan button is pressed, the room controller will switch to
displaying the configuration item number. To move to the next
setting, press the Mode button again and the “20” will be
displayed. Press the Up button and the display will change to
“21.” The Mode button will toggle the display between the
software configuration item number (i.e., “20,” “21,” etc.) and
the configuration value. The Up and Down buttons will change
either the item number or the value, which ever is displayed at
the time.
This mode will exit automatically after 30 seconds of
inactivity.
NOTE: If units are grouped to one room controller, all units
will have the same configuration value.
Service Test Mode — Prior to start-up, conduct the
Service Test mode to ensure the unit is ready for start-up.
There is a hidden Service Test mode that is initiated through
a combination of button presses when the remote is off. The
following buttons need to be pressed, in sequence, within
6 seconds:
1. Down arrow
2. Fan button
3. Up arrow
4. Fan button
5. Mode button
Once in Service Test mode, the Service Test mode message
will be sent, and Sr will be displayed in the temperature icons
until the Down button is pressed. During Service Test mode all
the icons are off, and the only button that is active is the Down
button. To cancel Service Test mode, press the Down button to
send a message of Off mode to the unit. Service Test mode
automatically times out after 30 minutes and the remote will
operate normally.
When test mode is selected, the unit will operate as
described below:
• The Unit Status (Green) and Timer (Yellow) LEDs blink
every 2 seconds.
• The indoor fan will operate according to user-selected
speed. If user selected speed is Auto, the fan will run in
High speed.
• If the unit is configured as an A/C Only unit, it will operate
in cool mode with demand.
• If the unit is configured as a Heat Pump unit, the louver will
operate according to user-selected position. If user selected
louver is Auto, louver operates according to auto heat or
cool louver based on operating mode.
• The unit will run in cool mode for 3 minutes, then it will run
in heat mode for 2 minutes, or until the indoor coil is greater
than 104 F The unit will run in cool mode until test mode is
exited.
S with Swing Louver Icon Represents the swing louver
A with Auto Louver Icon Represents the auto louver
ITEM VALUE COMMENT
20
1: Heat Pump
0: AC only (indoor unit with
or without electric heaters)
Unit Configuration
defaults to heat pump
21 1-199 in increments of 1
CCN Address of the unit.
Defaults to 1.
To display the hundreds,
push .
22 0-199 in increments of 1
Zone number -
Communications zone
the system is located in
Defaults to 0
To display the hundreds,
push .
24
0: Start in Off mode
1: Start in last active mode
Auto Restart
Defaults to “On”
Keep it pressed for
at least 5 seconds
Check the
value
Change the
value
up
down
Next
item
up
down
To check/change
the values of items
11 and 12 go back
to point A
A
Fig. 32 — Room Controller Configuration Steps