
21
UNIT MOUNTING (INDOOR)
Mounting Bracket – The fan coil units are furnished with
mounting brackets or dedicated mounting holes to hang the unit.
Support – Adequate support must be provided to handle the
weight of all fan coils. Refer to the Physical Data section for
weights, and the base unit dimensional drawings.
Unit Leveling – For reliable operation, units should be level in all
planes.
Clearances – Minimum clearance as shown in Fig. 13- 14.
Unit location – Select a location which will provide the best air
circulation for the room. These units should be positioned as high
to have adequate air circulation. The unit return and discharge
should not be obstructed by furniture, curtains, or anything which
may cause the unit to short cycle or air to recycle.
UNIT MOUNTING (OUTDOOR)
Support – A location which can bear the weight of outdoor unit.
Refer to the Physical Data section for weights, and base
dimensional drawings.
Unit Leveling – For reliable operation, units should be level in all
planes.
Clearances – Minimum clearances, as shown in Fig. 14, must be
provided for airflow. The outdoor units are designed for free- blow
applications. Air inlets and outlets should not be restricted.
Unit location – A location which is convenient to installation and
not exposed to strong wind.
SYSTEM OPERATING CONDITIONS
Cooling operating range:
Operating Range
Min / Max °F (°C)
Cooling Heating
Outdoor DB 4 / 122 (-20 / 50) 4 / 86 (-20 / 30)
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30)
Indoor WB 59 / 84 (15 / 29)
Heating operating range:
Non-Operating Temperature Range
Min / Max °F (°C)
Indoor/O utdoor DB 32 / 86 (0 / 30)
METERING DEVICES
The outdoor unit has multiple electronic expansion valves to
manage the refrigerant flow to the different indoor fan coils
connected to that unit.
REFRIGERANT LINES
General Guidelines:
1. The outdoor units are shipped with full charge of R- 410A
refrigerant. All charges, line sizing, and capacities are based
on runs of 25 ft (7.6 m). For runs over 25 ft (7.6m), consult
long- line section on this page for proper charge
adjustments.
2. Refrige rant li ne s should not be buri ed in the ground. If it is
neces sar y to bury the li nes, not mor e tha n 36 inches (914 mm)
should be buried. Provide a mi ni m um of 6 inch (152 mm)
verti cal r i se to service val ves to prevent r e fri gera nt migr ation.
3. Both lines must be insulated. Use a minimum of ½-inch
(12.7 mm) thick insulation. Closed - cell insulation is
recommended in all long- line applications.
4. Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into
the structure.
Long Line Applications:
S No change in line sizing is required.
Unit
Size
Total Line Length
ftper indoor unit
Additional Charge, oz/ft.
ft (m)
Min Max
10 - 25
(3 - 8)
>25 - 66
(8 - 20)
>66 - 82
(20 - 25)
>82 - 98
(25 - 30)
18
10
66
None 0.16
27 82
0.1636
98 0.16
48
DRAIN CONNECTIONS
Install drains to meet the local sanitation codes. If adequate gravity
drainage cannot be provided, a field installed condensate pump
accessory should be used. Refer to the Installation Instructions of
the condensate pump for detailed specifications. (Condensate
Pump built- in on Ducted and Cassette indoor units).
NOTE: The high wall fan coils have internal condensate trap.
An external trap is not required.
WIRING
The main power is supplied to the outdoor unit. Four field supplied
connecting cables from the outdoor unit to each of the indoor units
are: L1, L2, Ground, and S for communication between the
outdoor unit and each indoor unit.
CONTROL SYSTEM
The 38MG / 40MA / 40MB unit is equipped with a microprocessor
control to operate the system and give optimum levels of comfort
and operating efficiency.
There are microprocessor boards and thermistors located in both
the indoor and outdoor units. The thermistors monitor the system
operation and control the operating mode. The change in the
settings or the modes of operation, use the factory supplied
wireless remote control.
The 38MG / 40MA / 40MB unit has the following operating
modes:
S Fan Only
S Auto
S Heating (on Heat Pumps only)
S Cooling
S Dehumidification (Dry)
FAN ONLY - In Fan Only mode, the system filters and circulates
the room air without changing the room air temperature.
AUTO - In Auto mode, the system will automatically select one of
the following operating modes: cooling, heating or fan only based
on the difference between the room temperature and the set point
temperature.
HEATING - In the Heating mode, the system heats and filters
room air.
COOLING - When in Cooling mode, the fan runs all the time and
the system cools, dries and filters room air.
DEHUMIDIFICATION (DRY) - in Dehumidification (Dry)
mode, the system dries, filters and slightly cools room temperature.
This mode does not take place of a dehumidifier.
In addition to the above modes that are selected by using the
remote control, the unit can run in emergency mode by using a
manual button. This mode is used when the remote is misplaced or
the batteries in the remote have died. In this mode, the unit will run
in AUTO mode with a predetermined set point (76_F/24.4_C)
Comentarios a estos manuales