GUIDE SPECIFICATIONS
HORIZONTAL DISCHARGE OUTDOOR UNITS
Size Range:1 1/2, 2 1/4, 3 and 4 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 38MG
PART1–GENERAL
1.01 System Description
A. Outdoor air-cool ed split syste m compr ess or se cti ons sui tabl e for
on- the- ground, roof top, wa l l hung or balcony mounting. Unit s
shall consist of a variable speed rotary compressor, an air- cooled
coil, propell er- type draw- through outdoor fa n, re vers i ng val ve,
accumulator, electronic expansion valves, multiple service valves,
and controls that allows multiple indoor unit s to be connect ed to
the outdoor unit. Units shall discha rge hori zonta l ly as show n on
the cont rac t dra wings. Uni t s sha ll func t ion as the outdoor
com ponent of an air- to- air hea t pump system.
B. Units shall be used in a refrigeration circuit matched to two,
three, four , or five multi style heat pump fan coil units.
1.02 Agency Listings
A. Unit construction shall comply with ANSI/ASHRAE 15, latest
revision, and with NEC.\
B. Units shall be evaluated in accordance with UL standard 1995.
C. Units shall be listed in CEC directory .
D. Unit cabinet shall be capable of withstanding 500-hour salt
spray test per Federal Test Standard no. 141 (method 6061).
E. Air-cooled condenser coils shall be leak tested at 550 psig.
1.03 Delivery, Storage, And Handling
Units shall be shipped in one piece and shall be stored and handled
per manufacturer’s recommendations.
1.04 Warranty (For Inclusion B y Specifying
Engineer)
PART 2 PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air-cooled outdoor unit. Contained
within the enclosure shall be all factory wiring, piping, controls,
and compressor.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with baked-enamel finish on inside
and outside.
2. Unit access panel should be removable with minimal screws
and shall provide full access to the compressor, fan, and
control components.
3. Outdoor compartment shall be isolated and have an acoustic
lining to assure quiet operation.
C. Fans:
1. Outdoor fans shall be direct-drive propeller type, and shall
discharge air horizontally. Fan shall draw air through the
outdoor coil.
2. Outdoor fan motors shall be multi- speed, totally-enclosed,
single phase motors with permanently lubricated ball
bearings. Motor shall be protected by internal thermal
overload protection.
3. Shaft shall have inherent corrosion resistance.
4. Outdoor fan openings shall be equipped with metal/mesh
PVC coated protection grille over fan.
D. Compressor
1. Compressor shall be fully hermetic variable speed rotary
type.
2. Compressor shall be single phase, inverter driven.
3. Compressor shall be equipped with oil system, operating oil
charge, and motor.
4. Motor shall be suitable for operation in refrigerant and oil
atmosphere.
5. Compressor assembly shall be installed on rubber vibration
isolators.
6. The inverter and compressor shall be protected against over
temperature and over current.
E. Outdoor Coil:
Coil shall be constructed of Aluminum fins mechanically bonded
to seamless copper tubes, which are cleaned, dehydrated and
sealed.
F. Refrigerant Components:
Refrigerant circuit components shall include multiple brass external
liquid line service valves with service gauge connection port,
multiple suction line service valves with service gage connection
port, accumulator, reversing valve, electronic expansion valves.
G. Safeties:
Operating safeties shall be factory selected, assembled, and tested.
The minimum functions shall include the following:
1. Compressor discharge over temperature protection.
2. System low voltage protection.
3. Compressor overload protection.
4. Compressor over current protection.
5. IPM module protection.
H. Electrical Requirements:
1. Units shall operate on single-phase, 60 Hz power at
208/230 v.
2. Unit electrical power shall be a single point connection.
3. All power and control wiring must be installed per NEC
and all local electrical codes.
4. Units shall have multiple terminal blocks to connect to
multiple indoor units.