Carrier 40MBQB12C--3 Hoja de especificaciones Pagina 22

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 21
22
WIRELESS REMOTE CONTROL
1. A wireless remote control is supplied for system operation.
2. Each battery- operated wireless remote control may be used
to control more than one unit.
3. The wireless remote control has a range of 25 ft. (7.6 m).
Fig. 15 Wireless remote control
WIRED REMOTE CONTROL (STANDARD
ON DUCTED UNITS)
1. Optional wired remote controller used for system operation
of all high- wall, cassette and floor console units.
2. Kit includes a wired remote controller and a connecting
cable.
3. Connect with wire terminal between remote controller and
indoor unit.
4. Display in _For_C and temperature increments every 1_F
or every 1_C.
Fig. 16 Wired remote contr ol
SEQUENCE OF OPERATION
Simultaneous heating and cooling is not allowed. At start- up, the
first indoor unit to call for operation (heating or cooling) will
control from the preset position, the mode of operation for the rest
of the indoor units connected to the same outdoor unit. If the other
units conflict in mode with the first unit an error message will be
displayed on those units.
When a unit is set to COOL, HEAT or DRY mode, the electronic
expansion valve is first initialized (closed) and then is opened to a
preset position.
Superheat heat for each fan coil (the ones that are ener gized) is
monitored and the position of the electronic expansion valve is
adjusted to ensure that each fan coil gets the appropriate amount of
refr i gera nt t o mai nt ain the require d supe rhea t. Aft er the se t point is
sati sfied a nd the fa n coil shut s of f , the e lec t ronic expansion val ve stays
open for a spe cif ied ti me to ens ure tha t sys tem pre ssur es equalize.
When the system is set for COOL, HEAT or DRY mode, the
compressor speed is varied by comparing the indoor air
temperature with the set point and continuously adjusting the
compressor speed (to keep the compressor running as long as
possible) in an effort to maintain the greatest comfort possible.
The indoor fan can be running in MANUAL or AUTO mode.
When the fan is running in AUTO mode, the speed is determined
by comparing the room temperature to the set point.
In COOLING mode, when the set point is satisfied, the fan will
continue running. In HEATING mode, when the set point is
satisfied, the fan speed will be reduced and then will run
continuously until the coil temperature drops to a point cold air is
blown on the occupants in the space, at which time the indoor fan
is de- energized.
When the unit goes through the defrost cycle, the indoor fans are
de- energized and the refrigerant is circulated through all the fan
coils (even if they were off or on standby before the defrost cycle)
to maximize the heat transfer surface area available for defrost
operation.
Vista de pagina 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 35 36

Comentarios a estos manuales

Sin comentarios