GUIDE SPECIFICATIONS
INDOOR FLOOR CONSOLE DUCTLESS UNITS
Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*F
PART 1 - GENERAL
1.01 System Description
Indoor, wall- mounted, direct- expansion fan coils are matched with
a heat pump outdoor unit.
1.02 Agency Listings
Unit shall be rated per AHRI Standards 210/240 and listed in the
AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units shall be stored and handled per unit manufacturer’s
recommendations.
1.04 Warranty (For Inclusion B y Specifying
Engineer)
PART 2 - PRODUCTS
2.01 Equipment
A. General:
Indoor, direct- expansion, floor- mounted fan coil. Unit shall be
complete with cooling/heating coil, fan, fan motor, piping
connectors, electrical controls, microprocessor control system, and
integral temperature sensing. Unit shall be furnished with integral
mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet dischar ge and inlet grilles shall be attractively styled,
high- impact polystyrene. Cabinet shall be fully insulated for
improved thermal and acoustic performance.
CFans:
1. Fan shall be tangential dir e ct- drive blower type with air int ake in
the cente r of the unit and discharge at the top and bott om fr ont .
Auto mati c, mot or-dri ven vertical air swe ep shall be provided standar d.
2. Air sweep operation shall be user selectable. The vertical sweep
may be adjusted (using the remote control) and the horizontal air
direction may be set manually.
D. Coil:
Coil shall be copper tube with aluminum fins and galvanized steel
tube sheets. Fins shall b e bonded to the tubes by mechanical
expansion. A drip pan under the coil shall have a drain connection
for hose attachment to remove condensate. Condensate pan shall
have internal trap.
E. Motors:
Motors shall be open drip- proof, permanently lubricated ball
bearing with inherent overload protection. Fan motors shall be
3- speed.
F Controls:
Controls shall consist of a microprocessor- based control system
which shall control space temperature, determine optimum fan
speed, and run self diagnostics. The temperature control range shall
be from 62_Fto86_F(17_Cto30_C) in increments of 1_For
1_C, and have 46_F Heating Mode (Heating Setback). The
wireless remote controller shall have the ability to act as the
temperature sensing location for room comfort.
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same operating
conditions as at failure.
2. A timer function to provide a minimum 24- hour timer cycle for
system Auto Start/Stop.
3.T emperature- sensing controls shall sense return air temperature.
4. Indoor coil freeze protection.
5.Wireless infrared remote control to enter set points and operating
conditions.
6. Automatic air sweep control to provide on or off activation of air
sweep louvers.
7. De humidification mode shall provide increased latent removal
capability by modulating system operation and set point
temperature.
8. Fan- only operatio n to provide room air circulation when no
cooling is required.
9. Diagnostics shall provide continuous checks of unit operation
and warn of possible malfunctions. Error messages shall be
displayed at the unit.
10. Fan speed control shall be user- selectable: high, medium, low,
or microprocessor controlled automatic operation during all
operating modes.
11. Automatic heating- to- cooling changeover in heat pump mode.
Control shall include deadband to prevent rapid mode cycling
between heating and cooling.
12. Indoor coil high temperature protection shall be provided to
detect excessive indoor discharge temperature when unit is in heat
pump mode.
G. Filters: Unit shall have filter track with factory- supplied
cleanable filters.
H. Electrical Requirements: Indoor fan motor to operate on
208- 230V as specified. Power is supplied from the outdoor unit.
I. Operating Characteristics: The system shall have a minimum
SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI
conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to
connect from the left, right or back of unit. Both refrigerant lines
need to be insulated.
K. Special Featur es (Field Installed):
1. Condensate Pump: The condensate pump shall remove
condensate from the drain pan when gravity drainage cannot be
used. Pump shall be designed for quiet operation. Pump shall
consist of two parts: an internal reservoir/sensor assembly, and a
remote sound- shielded pump assembly. A liquid level sensor in
the reservoir shall stop cooling operation if the liquid level in the
reservoir is unacceptable.