PACKAGED TERMINAL COOLING UNIT
WITH HEAT PUMP OR ELECTRIC HEATING
HVAC Guide Specifications
Size Range: Cooling: 7,100 to 13,700 Btuh
Heating: 6,100 to 11,000 Btuh Heat Pump
6,400 to 17,000 Btuh Electric
Carrier Model Numbers: 52SC Cooling
Only Unit
52SE Unit with
Electric Heat
52SQ Heat Pump
Part 1 — General
1.01 SYSTEM DESCRIPTION
Single piece, thru-the-wall electrically controlled unit
using hermetic rotary compressor for cooling and heat
pump or electric resistance heat, as shown on the con-
tract drawings.
1.02 QUALITY ASSURANCE
Unit shall be rated in accordance with ARI Standard
310/380-93 and certified by UL and UL, Canada.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single-piece heating and/or
cooling unit. Contained within the unit enclosure
shall be compressor, coils, fans and fan motor, heat-
ing means, controls, all wiring and piping, and a
full refrigerant charge (R-22).
B. Front Panel (supplied with unit) and Wall Sleeve:
Wall sleeve and front panel shall be of plastic mate-
rial. Front panel to have louvers in front surface.
C. Fans and Motor:
1. Evaporator (indoor) fan shall be a single-inlet
squirrel cage blower with a corrosion-resistant
finish, discharging air upwards. Fan shall be
dynamically balanced.
2. Condenser (outdoor) fan shall be a propeller
type with corrosion-resistant finish, discharg-
ing air out the rear of the unit, and shall be
dynamically balanced.
3. Motor shall be totally enclosed, permanently
lubricated, and multiple speed.
D. Compressor:
The compressor shall be fully hermetic with inter-
nal and external vibration isolation.
E. Coils:
The coils shall have aluminum plate fins mechani-
cally bonded to seamless copper tubes internally
enhanced (grooved) with all joints brazed.
F. Refrigerant Components:
All piping, compressor, and expansion devices shall
be included.
G. Controls and Safeties:
1. Controls shall consist of pushbutton OFF/
FAN/ HEAT/COOL adjustable thermostat with
upper and lower limits, VENT OPEN/CLOSE,
and FAN CYCLE switches. Additional con-
trols for heat pumps include outdoor coil
defrost thermostat.
2. Safeties shall consist of automatic reset over-
temperature and overcurrent protection for
compressor,
inherent, automatic reset over-
temperature protection for
fan motor;
two
overtemperature protectors for
heater.
H. Operating Characteristics:
Unit shall be capable of starting and running at
115 F ambient outdoor temperature per maximum
load criteria of ARI Standard 310. Compressor with
standard controls shall be capable of operation
down to 25 F ambient outdoor temperature for heat
pump and 55 F ambient outdoor temperature for
cooling.
I. Electrical Requirements:
230/208-Volt: Shall be prewired with one plug to
use with appropriate wall receptacle as specified on
unit nameplate.
265-Volt: Shall be hard-wired or cord-connected
through subbase.
J. Filter:
1. One-piece washable type that filters supply air.
2. One-piece washable type filter in vent door fil-
ters outdoor air.
K. Corrosion Protection (CP):
Corrosion Protection (CP), for coastal or corrosive
environments, prolongs the life of the product. Min-
imum requirements are:
1. All outdoor-exposed sheet metal parts shall be
coated with a polyester thermostat powder coat
paint.
2. Compressor and outdoor fan motor finish shall
be capable of withstanding 500 hours of salt
spray testing per ASTM B-117.
3. Compressor mounting screws shall be Serma-
gard coated.
4. Outdoor coil fin stock shall be coated and able
to withstand 1000 hours of salt spray testing
per ASTM B-117.
5. Outdoor coil tube sheets must be made of 316L
stainless steel.
GUIDE SPECIFICATIONS