Software Revs 3,5,6,8,10, 12 Infinity /Evolution Troubleshooting (Rev. 2)
10-12-2006
22
TABLE 1
Advance Troubleshooting
Fan Coil / Furnace / 2-stage Communication Bus
FE Control Board
Furnace Control Board
Two-Speed Control Board
-Voltage Readings -
With board Power applied, and No U.I. connected, all other devices disconnected
A to B ~3 vdc
A to C ~3 vdc
B to C ~.01 to 0.3 vdc
C to D 24 vac
The above readings are meant to prove that the communication driver is not dead or shorted.
It does not guarantee that the unit will communicate. If communication problems exist and
voltage read good, an external short in the thermostat wiring, or a mis-applied accessory
may be the cause.
-Voltage Readings -
With board Power applied, and U.I. Applied, all other devices disconnected
A to B ~2.5 to 3.9 vdc (pulsating)
A to C ~2.5 to 3.9 vdc (pulsating)
B to C ~0.1 to 0.9 vdc (pulsating)
C to D 24 vac
The above readings are meant to prove the communication drivers are functioning, are not
open or shorted, and wiring between devices is OK. If voltages check out OK and
communication problems still exist, it could be a board problem.