Software Revs 3,5,6,8,10, 12 Infinity /Evolution Troubleshooting (Rev. 2)
10-12-2006
9
User Interface Generated Fault Descriptions cntd.
Fault
Description
User Interface Display Action
Original
Models
-A models
Outdoor unit
communication fault
ODU COMM
FAULT in fault
history
SYSTEM
MALFUNCTION
on main screen
OUTDOOR UNIT
COMMUNICATION FAULT
fault history
SYSTEM MALFUNCTION
on main screen
User interface has lost communication
with outdoor unit. Check wiring between
user interface and outdoor unit. Check
bus voltages on user interface and
outdoor unit. Also check for low voltage
short in outdoor unit control wiring.
Zone board 1
communication fault
ZONE 1-4 COMM FAULT in fault history
SYSTEM MALFUNCTION on main screen
User interface cannot communicate with
damper control module. Check bus
voltages and wiring.
Zone board 2
communication fault
ZONE 5-8 COMM FAULT in fault history
SYSTEM MALFUNCTION on main screen
User interface cannot communicate with
damper control module. Check bus
voltages and wiring.
NIM communication
fault
NIM COMM FAULT in fault history
SYSTEM MALFUNCTION on main screen
User interface cannot communicate with
NIM. Check bus voltages and wiring.
Defrost error DEFROST LOCKED in fault history
SYSTEM MALFUNCTION on main screen
The outdoor unit has been in defrost for
15 minutes.
Stage down due to
noise control
AIRFLOW
LIMITED. STAGE
DOWN
OCCURRED in
fault history
No display on
main screen
AIRFLOW LIMITED.
SHUTDOWN OCCURRED
In fault history
No display on main screen
A zone has reached its airflow limit setting
and the system has compensated by
staging down or shutting down. The
system is designed to do this to control air
noise, and this does not necessarily
reflect a problem with the system. See
detailed description in Zoning
Troubleshooting section.
Zone Board Fuse
blown
24 - ZONE BOARD FUSE in fault history
SYSTEM MALFUNCTION on main screen
Change fuse
Zone X Sensor 55 - ZONE SENSOR in fault history
NO SENSOR DATA on main screen for that
zone
Check zone sensor
LAT/HPT Sensor LAT/HPT SENSOR in fault history
No display on main screen.
Check sensor. These sensors are
optional and are for display purposes
only. The system does not react to LAT or
HPT temperature inputs.