PERFORMANCE AND ELECTRICAL DATA
MODEL 52SC (265V)
MODEL
NO.
COOLING
CAPACITY*
(Btuh)
EER
VOLT
RANGE
AMPS
COOLING
WATTS
COOLING
POWER
FACTOR
%
52SCD007---4 7,100 11.0
292-239
2.7 645 94
52SCE009---4 9,100 9.5 3.8 958 95
52SCC012---4 12,000 9.2 5.2 1,304 99
52SCC014---4 13,700 9.0 5.9 1,522 98
MODEL
NO.
FAN MOTOR
Horsepower
Full Load
Amps
Indoor CFM
HI/LO
52SCD007---4 1/15 0.56 280/200
52SCE009---4 1/8 0.7 350/300
52SCC012---4 1/6 0.8 380/310
52SCC014---4 1/8 0.7 350/250
MODEL
NO.
MAX. FUSE
SIZE
(Amps)
MIN.
CIRCUIT
AMPS
RECEPTACLE
TYPE†
R-22
CHARGE
(oz)
DEHUMIDIFICATION
(Pints/Hr)
APPROX.
CHASSIS
SHIP WT.
(lb)
52SCD007---4
15
4.0
A
23 3.0 125
52SCE009---4 5.6 27 2.1 120
52SCC012---3 6.5 36 3.4 129
52SCC014---3 8.1 35 4.2 130
LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310/380-93.
†All 265-v units require Accessory Hard-Wire Kit or the
Accessory Cord-Connected Kit for installation. Use of the
Accessory Cord-Connected Kit requires the installation of
the Subbase, along with a field-supplied receptacle. Recep-
tacle configurations of the Accessory Cord-Connected Kit
are shown at right.
RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE
VOLTAGE
265
OUTLET RATED VOLTS/AMPS 277/15 277/20 277/30
OUTLET BLADE CONFIGURATION
A B
C
FEMALE RECEPTACLE
MFG. PART NO.
Hubbell
Eagle
—
834B-BOX
—
834B-BOX
9315
—
TIME-DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
15 20 30
HACR — Heating, Air Conditioning, and Refrigeration
33
Comentarios a estos manuales