GUIDE SPECIFICATIONS
PACKAGED TERMINAL COOLING UNIT
WITH HEAT PUMP OR ELECTRIC HEATING
HVAC Guide Specifications
Size Range: Cooling: 7,100 to 13,700 Btuh
Heating: 6,100 to 11,000 Btuh Heat Pump
6,400 to 17,000 Btuh Electric
Carrier Model Numbers: 52SC Cooling Only
Unit
52SE Unit with
Electric Heat
52SQ Heat Pump
Part 1 — General
1.01 SYSTEM DESCRIPTION
Single piece, thru-the-wall electrically controlled unit
using hermetic rotary compressor for cooling and
heat pump or electric resistance heat, as shown on
the contract drawings.
1.02 QUALITY ASSURANCE
Unit shall be rated in accordance with ARI Stand-
ard 310/380-93 and certified by UL and UL, Canada.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufactur-
er’s recommendations.
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single-piece heating and/or cool-
ing unit. Contained within the unit enclosure shall
be compressor, coils, fans and fan motor, heating
means, controls, all wiring and piping, and a full
refrigerant charge (R-22).
B. Front Panel (supplied with unit) and Wall Sleeve:
Wall sleeve and front panel shall be of plastic ma-
terial. Front panel to have louvers in front surface.
C. Fans and Motor:
1. Evaporator (indoor) fan shall be a single-inlet
squirrel cage blower with a corrosion-resistant
finish, discharging air upwards. Fan shall be dy-
namically balanced.
2. Condenser (outdoor) fan shall be a propeller type
with corrosion-resistant finish, discharging air out
the rear of the unit, and shall be dynamically
balanced.
3. Motor shall be totally enclosed, permanently lu-
bricated, and multiple speed.
D. Compressor:
The compressor shall be fully hermetic with inter-
nal and external vibration isolation.
E. Coils:
The coils shall have aluminum plate fins mechani-
cally bonded to seamless copper tubes internally
enhanced (grooved) with all joints brazed.
F. Refrigerant Components:
All piping, compressor, and expansion devices shall
be included.
G. Controls and Safeties:
1. Controls shall consist of pushbutton OFF/FAN/
HEAT/COOL adjustable thermostat with upper
and lower limits, VENT OPEN/CLOSE, and FAN
CYCLE switches. Additional controls for heat
pumps include outdoor coil defrost thermostat.
2. Safeties shall consist of automatic reset over-
temperature and overcurrent protection for com-
pressor, inherent, automatic reset over-temperature
protection for fan motor; two over-temperature
protectors for heater.
H. Operating Characteristics:
Unit shall be capable of starting and running at 115 F
ambient outdoor temperature per maximum load
criteria of ARI Standard 310. Compressor with stand-
ard controls shall be capable of operation down to
25 F ambient outdoor temperature for heat pump
and 55 F ambient outdoor temperature for cooling.
I. Electrical Requirements:
230/208-Volt: Shall be prewired with one plug to
use with appropriate wall receptacle as specified
on unit nameplate.
265-Volt: Shall be hard-wired or cord-connected
through subbase.
J. Filter:
1. One-piece washable type that filters supply air.
2. One-piece washable type filter in vent door fil-
ters outdoor air.
K. Special Features:
Certain standard features are not applicable when
the features designated are specified. Contact
your local Carrier Sales Office for amending
specifications.
1. Factory-installed electric heater for use with
heat pump or heat/cool units
2. RC — Remote control permits unit control from
remote thermostat
3. CP — Corrosion protection provides for extra
paint on control box, partition top cover and
exterior coil
4. Standard grille (aluminum)
5. Architectural grille (plastic or aluminum)
6. Hard-wire kit
7. Drain kit
8. Subbase
9. Wall sleeve
10. Lateral duct kit
11. Energy management accessory kit
12. Cord-connection kit (265 V)