30GX and 30HXC series
PRO-DIALOG Control
Screw-Compressor Air- and
Water-Cooled Liquid Chillers
50 Hz
GLOBAL CHILLER
Vista de pagina 0
1 2 3 4 5 6 ... 35 36

Indice de contenidos

Pagina 1 - Water-Cooled Liquid Chillers

30GX and 30HXC seriesPRO-DIALOG ControlScrew-Compressor Air- andWater-Cooled Liquid Chillers50 HzGLOBAL CHILLER

Pagina 2

10The summary interface (right hand section) includes a mimicdiagram of the unit, together with push-buttons and LEDs. Itgives quick access to the mai

Pagina 3 - Table of contents

11kPakPa4.3 - Menus4.3.1 - Selecting a menuThe MENU button authorises you to select a menu from the10 main menus that are available. Each time you pre

Pagina 4

12 STATUSTEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURATIONALARMSUSER[USEr]SERVICE[SErviCE]FACTORY[FACtorY]RUNTIME 1[RuntiME 1]MAINTE-NA

Pagina 5

13MENULegend** Displayed if the alarm exists- Not in useITEM012345678910111213141516171819STATUSDefault displayActive modesChiller occupied/unoccupied

Pagina 6

14INFORMATION MENU (3)ITEM FORMAT UNITS0±nn.n °CLOFF -L-On -L-Sc -CCn -rEM -MASt -OFF -rEADY -dELAY -StOPPing -running -triPout -OvErridE -OCCUPIEd -U

Pagina 7

15DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)MODE # MODE NAME7 Delay at start-up active8 2nd cooling setpoint active9 Setpoint res

Pagina 8

16SETPOINTS MENU [2]ITEM FORMAT UNITS RANGE0 ±nn.n °C See table below1 ±nn.n °C See table below2 nnn °C See table below3 [1] nnn °C See table below4 [

Pagina 9

174.5.5 - Description of the Inputs menuINPUTS MENU [2]ITEM FORMAT UNITS0 OPEn/CLoS -1 OPEn/CLoS -2[1] OPEn/CLoS -3[3] OPEn/CLoS -4 OPEn/CLoS -5 OPEn/

Pagina 10

18OUTPUTS STATUS AND TESTS MENU [2] [3]ITEM FORMAT UNITS01----2 [1]----3 [1] tEST----4 [1] tEST----5 tEST %6 tEST %7 tESt----8 tESt--9 tESt--10 tESt

Pagina 11

19OUTPUTS STATUS 2 AND TESTS MENU [2] [3]ITEM FORMAT UNITS01 [1] tESt 0 - 82 [1] tESt 0 - 83 tESt--4 tESt %5 tESt %6 [1] tESt %7 [1] tESt %8On-Sto

Pagina 12 - 4.4 - General menu structure

2The cover illustrations are solely for illustration, and form no part of any offer for sale or any sale contract. The manufacturerreserves the right

Pagina 13 - 4.5 - Menu tree structure

204.5.6.3 - Manual testsThis function allows the user to test the outputs individually, ifthe machine is completely shut down (LOFF). To carry out ama

Pagina 14

21SUB-MENU PERIOD CONFIGURATION*Item PERIOD 1 to 8[PEriod X MEnu]*0 Return to previous menu1 Start of occupied period2 End of occupied period3 Selecti

Pagina 15

224.5.7.3 - Description of the User 1 Configuration sub-menuUSER 1 CONFIGURATION SUB-MENU [2]ITEM FORMAT UNITS DEFAULT COMMENTS0 USEr MEnu - - When se

Pagina 16

234.5.7.4 - Description of the User 2 Configuration sub-menuUSER 1 CONFIGURATION SUB-MENUITEM FORMAT UNITS DEFAULT COMMENTS0 USEr 2 Menu When selected

Pagina 17

24PERIOD X CONFIGURATION SUB-MENUS (X = 1 to 8)ITEM # FORMAT COMMENTS0 Period X Menu Indicates the period (X) you are going to configure.When selected

Pagina 18

25BROADCAST CONFIGURATION SUB-MENUITEM # FORMAT COMMENTS0 broAdCASt MEnu When selected this item authorises a return to the main menu.1 YES/no Determi

Pagina 19

264.5.10 - Runtime menu descriptionRUNTIMESRUNTIMES 1[runtiMES 1]RUNTIMES 2[runtiMES 2]MAINTENANCE[MAintEnAnCE]NOTE: The items in brackets show what i

Pagina 20

275 - PRO-DIALOG PLUS CONTROL OPERATION5.1 - Start/stop controlThe table below summarises the unit control type and stop orgo status with regard to th

Pagina 21

285.3 - Evaporator water pump controlThe unit can control one or two evaporator water pumps. Theevaporator water pump is turned on when this option is

Pagina 22

295.8 - Demand limitGenerally, demand limit is used by an energy managementsystem in order to restrict the unit electricity consumption.The PRO-DIALOG

Pagina 23

3Table of contents1 - SAFETY CONSIDERATIONS ...

Pagina 24

30avoiding liquid slugging at the compressors and ensuringoperating stability.5.15 - Motor cooling valve controlThe temperature of the motor windings

Pagina 25

31Master/slave operation requires the connection of a temperatureprobe at the common manifold on each machine, if the heatexchanger leaving water temp

Pagina 26

326 - DIAGNOSTICS - TROUBLESHOOTING6.1 - GeneralThe PRO-DIALOG Plus control system has many fault tracingaid functions. The local interface and its va

Pagina 27

336.4 - Alarm codesThe following list gives a complete description of each alarmcode and its possible cause.DESCRIPTIONEvaporator entering fluid therm

Pagina 28

34RESET TYPECCN/AutomaticAutoDittoAuto in the10mn thatfollowDittoAuto if thesame alarmhas nottripped thesame dayDittoDittoDittoDittoDittoDittoDittoMan

Pagina 29 - Maximum permitted capacity

35ALARM CODE DESCRIPTION (CONT.)DESCRIPTIONLow oil pressure compr B2Evaporator frost protectionCondenser frost protection, circuitACondenser frost pro

Pagina 30

.Order No. 13054-76 (Phase 3 ), 04.2002. Supersedes order No.: 13054-76, 04.2000 Manufactured by: Carrier S.A., Montluel, France.Manufacturer reserve

Pagina 31

41 - SAFETY CONSIDERATIONS1.1 - GeneralInstallation, start-up and servicing of equipment can be hazard-ous if factors particular to the installation

Pagina 32

53 - HARDWARE DESCRIPTION3.1 - GeneralControl boardThe various control components are arranged in moduleswithin the control cabinet:• Control module:

Pagina 33 - 6.4 - Alarm codes

63.2.7 - Light emitting diodes on boardsAll boards continuously check and indicate the properoperation of their electronic circuits. A light emitting

Pagina 34

73.3.3 - The evaporator pumpIn appropriate cases the controller can also regulate an evapo-rator pump. This facility does not require an additional bo

Pagina 35

8DESCRIPTIONAlarm relay output, circuit AAlarm relay output, circuit BCritical fault relay outputUser safety loop and chilledwater pump interlockRemot

Pagina 36

9kPaMAIN INTERFACEBUTTON NAME DESCRIPTIONMenu Permits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if activ