18
OUTPUTS STATUS AND TESTS MENU [2] [3]
ITEM FORMAT UNITS
0
1
-
-
-
-
2 [1]
-
-
-
-
3 [1] tEST
-
-
-
-
4 [1] tEST
-
-
-
-
5 tEST %
6 tEST %
7 tESt
-
-
-
-
8 tESt
-
-
9 tESt
-
-
10 tESt
-
Legend
1 This item is displayed in certain unit configurations only
2 A test is only possible if the units are in local off mode and if all compressors have stopped
3 The password is only valid for the test. 'Test' is displayed during the test, alternating with the item number
4.5.6 - Description of the Outputs/Tests menu
4.5.6.1 - General
This menu displays the status of the controller outputs. More-
over, when the machine is fully stopped (LOFF) the outputs
can be activated for manual or automatic tests (the access to
the tests is password controlled).
4.5.6.2 - Menu description
DESCRIPTION
This item returns you to the previous menu.
Compressor status
b1 = compressor A1
b2 = compressor A2
b3 = compressor B1
b4 = compressor B2
The compressor status cannot be forced
Loader status
b1 = loader 1 circuit A
b2 = loader 2 circuit A
b3 = loader 1 circuit B
b4 = loader 2 circuit B
This item permits display of the loader status in circuits A or B. It also permits independent testing. In test mode the direction
arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.
Motor cooling valve status/test circuit A
b1 = main valve compressor A1
b2 = additional valve or economizer compressor A1
b3 = main valve compressor A2
b4 = additional valve or economizer compressor A2
This item permits display of the motor cooling valve status in circuit A. It also permits independent testing. In test mode the
direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.
Motor cooling valve status/test circuit B
b1 = main valve compressor B1
b2 = additional valve or economizer compressor B1
b3 = main valve compressor B2
b4 = additional valve or economizer compressor B2
This item permits display of the motor cooling valve status in circuit B. It also permits independent testing. In test mode the
direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.
Motor cooling valve cycle status/test, circuit A
Only for units with economizer
Motor cooling valve cycle status/test, circuit B
Only for units with economizer
Oil solenoid valve status/test
b1 = oil solenoid valve compressor A1
b2 = oil solenoid valve compressor A2
b3 = oil solenoid valve compressor B1
b4 = oil solenoid valve compressor B2
This item permits display of the different compressor valves.
It also permits independent testing. In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so
as to in turn force authorisation of each output.
Refrigerant shut-off valve status/test
Only for units with evaporator heater
b1 = Shut-off valve, circuit A
b2 = Shut-off valve, circuit B
In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each heater output.
Oil heater output status/test, circuits A and B
b1 = oil heater, circuit A
b2 = oil heater, circuit B
In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each heater output.
Oil pump output status/test, circuits A and B
b1 = oil pump, circuit A
b2 = oil pump, circuit B
In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each oil pump
output.