ALARM FUNCTION DESCRIPTION ACTION RESET NOTE
1xx Defect compressor A1 See SCPM subcodes below See SCPM subcodes below Manual
2xx Defect compressor A2 See SCPM subcodes below See SCPM subcodes below Manual
3xx Defect compressor B1 See SCPM subcodes below See SCPM subcodes below Manual
4xx Defect compressor B2 See SCPM subcodes below See SCPM subcodes below Manual
FUNCTION
High motor
temperature
Motor temperature
sensor
High pressurestat
tripped
High motor current
Rotor blocked
Ground current fault
Current drop in one
phase L1
Current drop in one
phase L2
Current drop in one
phase L3
Current imbalance
>14%
Current imbalance
>18%
No motor current
Star-delta start-up
Contactor failure
Compressor shut-
down not possible
Current phase reversal
Configuration block
fault
SCPM SUBCODES (XX)
ALARM
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
DESCRIPTION
SCPM detects high motor temperature, if
temperature is higher than 110°C for 10
seconds
SCPM measures a temperature outside
the -40°C to 118°C temperature range
HPS port to SCPM module open
SCPM detects high current, based on MTA
rating
SCPM detects ground current (2.5 +2/- 0
amps)
SCPM measures a current drop > = 65%
SCPM measures a current drop > = 65%
SCPM measures a current drop > = 65%
SCPM measures a current imbalance
between phases as more than 14% for 25
minutes
SCPM measures a current imbalance
between phases of more than 18% for 25
minutes
SCPM module shows less than 10% of the
MTA for more than 3 seconds
SCPM detects 10% of the MTA for 10
seconds after shutdown of the compressor
contactor. Oil solenoid still has supply.
SCPM detects a current phase reversal
via the core
SCPM detects a reading fault at the block
ACTION
Compressor shut down
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
None, simple message
Compressor shut down,
if threshold alarm is
validated.
Shut down
Compressor shut down
Unit shut down
Circuit shut down
Compressor shut down
Compressor shut down
RESET
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual, if
threshold alarm is
validated.
Otherwise auto
reset.
Ditto
Manual
Manual
Manual
Manual
Manual
Manual
NOTE
Solenoid, cooling motor defect, low
refrigerant charge. Wiring, motor
temperature sensor or SCPM board fault
Thermistor, solenoid, motor cooling or wiring
fault
Lack of condenser water flow. Condenser
valve blocked, fan circuit fault, high
condenser entering air or water temperature
Operation outside the compressor capacity.
Configuration block badly perforated, motor
fault
Load too high
Ground current fault on motor winding, wiring
fault
Motor fault, wiring fault
Motor fault, wiring fault
Motor fault, wiring fault
Loss of power supply, wiring fault, loose
terminal, core defective
Poor power supply, loose terminal, core
defective
Power supply interrupted, fuse(s) blown,
wiring fault, core defective
Defective connector
Defective/blocked contactor
Contact stuck
Supply phases or cables reversed, core
wiring reversed after replacement
Configuration block on SCPM board badly
perforated or badly placed. Defective board.
Legend:
* Defrost threshold = 1,1°C for water or for the lowest cooling setpoint less 4,4°C for brine or low brine.
** This safety circuit is controlled by two contacts, 16A and 16B, which are connected in series internally. If there is only a single control box there is a jumper on
16B, otherwise 16B controls the control box safety of the circuit. If one of the two contacts 16A and 16B is open, the whole unit is in fault status.
SCPM: Compressor protection module
FSM: Flotronic System Manager
TM
CSM: Chiller System Manager
MTA: Compressor Must Trip Amperes