34
RESET
TYPE
CCN/
Automatic
Auto
Ditto
Auto in the
10mn that
follow
Ditto
Auto if the
same alarm
has not
tripped the
same day
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Manual
Manual
Auto if the
same alarm
has not
tripped the
same day
Ditto
Manual
Manual
Auto if the
same alarm
has not
tripped the
same day
Ditto
Manual
Manual
Manual
Manual
Auto
Auto
Auto if the
same alarm
has not
tripped the
same day
Ditto
Ditto
DESCRIPTION
Unit emergency stop
Initial factory configuration
required
Illegal initial factory configuration
Compr A capacity too high
Compr B2 configured and
compressor B1 absent
Fan configured for a water-cooled
condenser
Fans not configured
Heat reclaim option configured
and reclaim sensors configured
Discharge pressure circuit A too
high
Discharge pressure circuit B too
high
Oil solenoid failure, compressor
A1
Oil solenoid failure, compressor
A2
Oil solenoid failure, compressor
B1
Oil solenoid failure, compressor
B2
Pre-start oil pressure,
compressor A1
Pre-start oil pressure,
compressor A2
Pre-start oil pressure,
compressor B1
Pre-start oil pressure,
compressor B2
Oil level circuit A low
Oil level circuit B low
Low saturated suction temp, crt A
Low saturated suction temp,
circuit B
High saturated suction temp,
circuit A
High saturated suction temp,
crt B
Low discharge superheat,
circuit A
Low discharge superheat, crt B
Max. oil pressure difference,
compressor A1
Max. oil pressure difference,
compressor A2
Max. oil pressure difference,
compressor B1
Max. oil pressure difference,
compressor B2
Loss of commuincation with
System Manager
Loss of communication with
master or slave unit
Low oil pressure compr A1
Low oil pressure compr A2
Low oil pressure compr B1
WHY WAS THIS ALARM
GENERATED?
CCN command to stop the unit received
All factory parameters are 0
Bad factory configuration
SCT>loadshed threshold. Max. satur. condensing
pressure (mct_sp) if only one capacity stage remains
in operation.
SCT>loadshed threshold. Max. satur. condensing
pressure (mct_sp) if only one capacity stage
remains in operation.
Oil pressure differential >17kPa during the period
following pump start-up and before opening of the oil
solenoid (see prelubrication)
Ditto
Ditto
Ditto
Oil pump does not sufficiently increase the pressure
during several prelubrication cycles
Oil pump does not sufficiently increase the pressure
during several prelubrication cycles
Oil pump does not sufficiently increase the pressure
during several prelubrication cycles
Oil pump does not sufficiently increase the pressure
during several prelubrication cycles
Oil level control contact open during operation
Oil level control contact open during operation
SST under defrost theshold* for 3 minutes
SST under defrost threshold* for 3 minutes
After 90 seconds of operation if SST > 12,8°C & EXV
< 1%
After 90 seconds of operation if SST > 12,8°C &
EXV < 1%
Superheat <2,8 K for 10 minutes
Superheat <2,8 K for 10 minutes
(Discharge pressure - oil pressure) >340 kPa for
more than 6 seconds
(Discharge pressure - oil pressure) >340 kPa for
more than 6 seconds
(Discharge pressure - oil pressure) >340 kPa for
more than 6 seconds
(Discharge pressure - oil pressure) >340 kPa for
more than 6 seconds
The unit is controlled by a System Manager
(Flotronic or Chiller) and communication with this
module is lost for more than two minutes
The master/slave link is broken due to a loss of
communication between the two units for more than
2 minutes
Oil pressure differential below the setpoint
(dynamically calculated) for 15 seconds
Oil pressure differential below the setpoint
(dynamically calculated) for 15 seconds
Oil pressure differential below oil setpoints 1 or 2
(see alert criteria for low oil pressure and setpoint)
ACTION TAKEN BY
THE CONTROL
Unit shut down
Unit cannot start
Ditto
Circuit A shut down
Circuit B shut down
Compressor A1 not
authorised to start
Compressor A2 not
authorised to start
Compressor B1 not
authorised to start
Compressor B2 not
authorised to start
Compressor A1cannot start
Compressor A2 cannot start
Compressor B1 cannot start
Compressor B2 cannot start
Circuit A shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
Compressor A1 shut down
Compressor A2 shut down
Compressor B1 shut down
Compr B2 shut down
Unit returns to autonomous
operating mode
Unit returns to autonomous
operating mode
Compressor A1 shut down
Compressor A2 shut down
Compressor B1 shut down
PROBABLE CAUSE
Control network
No factory configuration
Factory configuration error
Transducer/high pressure switch or fan
circuit defective, water flow obstructed in
the condenser, water entering
temperature or condenser air too high
Ditto
Oil valve defective
Ditto
Ditto
Ditto
Low oil level, oil pump, oil solenoid or oil
transducer failure
Ditto
Ditto
Ditto
Oil level detector defective, oil quantity
insufficient
Ditto
Low refrigerant charge, filter drier
obstructed, expansion valve and
transducer defective, low water flow, low
evaporator water temperature
Ditto
Expansion valve, liquid level sensor or
transducer defective, high evaporator
temp.
Ditto
Thermistor, transducer, EXV or
economizer defective
Ditto
Obstructed oil filter, oil solenoid or shut-
off valve blocked, or manual oil valve
closed
Ditto
Ditto
Ditto
Defective CCN BUS wiring or system
module failure
Defective CCN BUS wiring or loss of
supply
Low condenser air or water
temperature, oil filters obstructed, oil
valve blocked, oil solenoid and oil
pressure transducer defective
Ditto
Ditto
ALARM
CODE
41
42
43-n
43-1
43-2
43-3
43-4
43-5
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70