6.4 - Alarm codes
The following list gives a complete description of each alarm
code and its possible cause.
DESCRIPTION
Evaporator entering fluid thermistor failure
Evaporator leaving fluid thermistor failure
Condenser entering fluid thermistor failure
Condenser leaving fluid thermistor failure
Condenser entering fluid thermistor failure
Condenser leaving fluid thermistor failure
Outdoor temperature sensor fault
CHWS (master/slave) fluid thermistor fault
Compressor A1, discharge gas sensor
Compressor A2, discharge gas sensor
Compressor B1, discharge gas sensor
Compressor B2, discharge gas sensor
External 0-10 V dc signal fault
Discharge pressure transducer failure,circuit A
Discharge pressure transducer failure, circuit
B
Suction pressure transducer failure, crt A
Suction pressure transducer failure, crt B
Oil pressure transducer failure, compr A1
Oil pressure transducer failure, compr A2
Oil pressure transducer failure, compr B1
Oil pressure transducer failure, compr B2
Economizer A1 transducer failure
Economizer A2 transducer failure
Economizer B1 transducer failure
Economizer B2 transducer failure
Pressure sensor failure - coil pump down
circuit A
Pressure sensor failure - coil pump down
circuit B
Fault in the motor cooling valve position
sensor, circuit A
Fault in the motor cooling valve position
sensor, circuit B
Loss of communication with SCPM A1 board
Loss of communication with SCPM A2 board
Loss of communication with SCPM B1 board
Loss of communication with SCPM B2 board
Loss of communication with EXV board
Loss of communication with fan board #1
Loss of communication with fan board # 2
Loss of communication with auxiliary board
type 1
Loss of communication with heat reclaim or
evaporator heater board
'CCN/clock board' fault
Control box thermostat fault or phase reversal
WHY WAS THIS
ALARM GENERATED?
Thermistor outside range -40 to
118°C
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Signal outside range
Measured signal = 0V dc
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
SCPM A1 board does not respond
SCPM A2 board does not respond
SCPM B1 board does not respond
SCPM B2 board does not respond
4xDO board associated with the
EXV does not respond
4xDO board controlling the first four
fan stages does not respond
4xDO board controlling the fan
stages of circuit B does not
respond
Board does not respond
Analogue board does not respond
CCN/clock board is no longer
detected
Sensor overheated
ACTION TAKEN BY
THE CONTROL
Unit shut down
Unit shut down
None, simple message
None in cooling mode
Unit shut down in heating mode
None, simple message
None
Reset based on deactivated outdoor
sensor
Master/slave function deactivated
Compressor A1 shut down
Compressor A2 shut down
Compressor B1 shut down
Compressor B2 shut down
1- Loadshed: not used
2- Demand limit: deactivated
Circuit A shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
Compressor A1 shut down
Compressor A2 shut down
Compressor B1 shut down
Compressor B2 shut down
Circuit A shut down for unit with
economizer. Otherwise compressor
A1 shut down.
Compressor A2 shut down
Circuit B shut down for unit with
economizer. Otherwise compressor
B1 shut down.
Compressor B2 shut down
Circuit A remains in cooling mode
Circuit B remains in cooling mode
None
None
Compressor A1 shut down
Compressor A2 shut down
Compressor B1 shut down
Compressor B2 shut down
Unit shut down
Unit shut down if number of fan
stages by circuit is lower than three.
Otherwise circuit A shut down.
Circuit B shut down
Unit shut down if heating mode has
been selected.
Unit shut down if heat reclaim mode is
selected.
Unit shut down
Unit shut down
RESET TYPE
Auto, if the temperature
measured by the sensor
becomes normal again
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Automatic
Automatic if board is again
detected
Ditto
Auto if the same alarm has
not tripped the same day
PROBABLE
CAUSE
Thermistor or
wiring fault or
cable/wire
damaged
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Thermistor,
solenoid, motor
cooling or wiring
fault
Ditto
Ditto
Ditto
Defective input or
wiring fault
Defective
transducer, wiring
fault
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Wiring fault,
incorrect address
or defective board
Ditto
Ditto
Ditto
Ditto
Ditto
Ditto
Bus wiring fault,
incorrect address
or defective board
Auxiliary board
faulty
Faulty connection
Defective CCN/
clock board
Badly ventilated
control box
ALARM
CODE
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40**