Installation
10 RTU Open
1 Turn
the RTU Open's power. The controller reads the address each time you apply power to it.
2 Using the rotary switches, set the
(
) switch to the tens digit of the address, and set the
(
) switch to the ones digit.
To set the RTU Open’s address to 01, point the arrow on the
(
) switch to 0 and the
arrow on the
(
) switch to 1.
3 Turn on the RTU Open's power.
The factory default setting is
and must be changed to successfully install your RTU Open.
To set the RTU Open's communications protocol and baud rate
RTU Open's
DIP switches are used to set the controller's protocol and baud rate. The protocol and speed
selection is determined by the network on which the controller will be installed. For Carrier BACnet
implementations, select MS/TP @ 76.8 k as follows:
1 Power down the RTU Open. The controller reads the protocol and baud rate each time you apply power to
it.
2 Set
DIP switches 1, 2, and 4 to
to configure the controller for BACnet MS/TP and 76.8 k baud.
3 Power up the RTU Open.
Other protocols and baud rates are available. See the RTU Open Integration Guide for additional
instructions.