RTU Open 45
The cooling relays are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm. They
calculate the desired number of stages needed to satisfy the space by comparing the
Space Temperature
to
the:
Effective Occupied Cooling Setpoint
when occupied
Effective Unoccupied Cooling Setpoint
when unoccupied
When the cooling algorithm preconditions have been met, the compressors are energized in stages, as
applicable. Anti-recycle timers are employed to protect the equipment from short-cycling. There are fixed
three-minute minimum on-times, and five-minute off-times for each compressor output.
During compressor operation, the RTU Open may reduce the number of active stages if the rooftop supply air
temperature falls below the
Minimum Cooling SAT Setpoint
. A compressor staged off in this fashion may be
started again after the normal time-guard period has expired, if the
Supply Air Temperature
has increased
above the
Minimum Cooling SAT Setpoint
.
Compressor 2 Service Alarm Timer
functions are available (one for each stage of compression). This function
tracks the number of compressor run hours and generates an alarm when the accumulated runtime exceeds
the threshold set by the adjustable compressor service alarm timers.
Economizer
The RTU Open provides an analog economizer output for rooftop units with economizer dampers. Economizer
dampers may be used to provide indoor air quality control and free cooling when outside air conditions are
suitable.
The following conditions must be true for economizer operation:
The
Outdoor Air Temperature
is less than the
Space Temperature
and less than the
Economizer High
OAT Lockout Temp
setpoint
The indoor fan has been on for at least 30 seconds
The unit has a valid
Supply Air Temperature
input
The unit has a valid
Space Temperature
input
If any of the preceding conditions are not true, the economizer will be set to the
Vent Dmpr Pos / DCV Min
Pos
setpoint.
If all preceding conditions are true, the economizer PID loop will modulate the damper from the
Vent Dmpr
Pos / DCV Min Pos
setpoint.
The economizer moves to the
Vent Dmpr Pos / DCV Min Pos
setpoint if the SAT falls below the
Minimum
Cooling SAT
(+ 5°F).