RTU Open 13
- 5
- 6
- 7
- 8
- 7 & 8
- 4 & 6
- 1 & 3
- Analog Input
- Analog Output
- Digital Input
- Digital Output
*
- 24 Vac required at this wire to provide
status. Provide a jumper from
- 1 to
- 9 if no
safeties are utilized. See To wire inputs and outputs (page
14) for additional information on the RTU Open wiring harness assembly
terminations.
** Default input function
*** Parallel screw terminal at
(
- 1 =
- 6,
- 3 =
- 10,
- 5 =
- 2) may be used in place of the associated flying leads at
the harness (Part #OPN-RTUHRN). See To wire inputs and outputs (page
14) for additional information.
Input wiring specifications
Thermistor 1000 feet
(305 meters)
22 AWG Unshielded
4-20 mA 3000 feet
(914 meters)
22 AWG Unshielded
Binary input
1000 feet
(305 meters)
22 AWG Unshielded
SPT (RNET) 500 feet
(152 meters)
22 AWG
4 conductor
Unshielded
Comentarios a estos manuales