Time Guard Override may also be initiated from CCN by
setting TGO option in SERVICE table from OFF to ON.
The random 1 to 63 seconds is also applied to the indoor-
fan motor on power up, only.
Economizer Operation (VAV, CV, and Heat Pump
with CCN Sensors)
The economizer dampers will
open to provide free cooling and/or air quality control when
the outside conditions are suitable. It is accomplished by con-
trolling supply-air temperature to a certain level determined
by the Economizer Submaster Reference (ECONSR).Air qual-
ity control is driven by the IQMP (indoor-air quality mini-
mum position) calculated by the IAQ algorithm. The IQMP
will increase as the need for fresh air becomes greater. This
algorithm will calculate the submaster reference tempera-
ture ECONSR based on atmospheric conditions and cooling
requirements. The ECONSR value will be passed to the econo-
mizer submaster loop, which will modulate dampers to main-
tain SAT at ECONSR level. The Economizer inputs and out-
puts are shown in Tables 9 and 10.
Table 9 Economizer Inputs
INPUTS TYPE
Unit Type User Configured
Fan State Internal Parameter
Current Mode Internal Parameter
Space Temperature (SPT) Analog Input
Supply-Air Temperature
(SAT)
Analog Input
Return-Air Temperature
(RAT)
Analog Input
Outdoor-Air Temperature
(OAT)
Analog Input
Enthalpy Discrete Input
Stages of DX Cooling Internal parameter
Occupied Cooling Set Point
(OCSP)
User Configured, default = 78° F
Occupied Heating Set Point
(OHSP)
User Configured, default = 68° F
Supply-Air Set Point (SASP) User Configured, default = 55° F
High OAT Economizer
Lockout (OATL)
User Configured, default = 65° F
Space Temp. Reset Internal Parameter
External SAT Reset Internal Parameter
Table 10 Economizer Outputs
OUTPUTS TYPE
ECONSR Economizer Submaster Reference
SEQUENCE OF OPERATION
1. The control will check the following qualifying condi-
tions if atmospheric cooling is possible:
THERMOSTAT UNITS:
thermostat is calling for Cool, indoor fan is ON
enthalpy is low
SAT reading is available (or Compressors are ON)
OAT reading is available
•OATOATL
economizer position is NOT forced
SENSOR CONTROLLED UNITS:
indoor fan has been ON for at least 30 seconds
enthalpy is low
OAT reading is available
CV units: SPT reading is available
VAV units: SPT or RAT reading is available
VAV Units: SAT reading is available (or compressors
are ON)
•OATTEMP, where TEMP is SPT (CV), RAT, or SPT
(VAV)
VAV units with OHEN (Occupied Heating Enable) en-
abled, and TEMP OHSP + 1.0, where TEMP is RAT,
or SPT if RAT reading is not available
Economizer position is NOT forced
unit is not in heat mode
If any of the above conditions are not met, the ECONSR
will be set to its MAX limit. The next 2 steps will be
skipped.
2. If stages of DX cooling are greater than 0, ECONSR is
set to its minimum limit and the next step is skipped.
3. Calculate submaster reference ECONSR as follows:
THERMOSTAT UNITS:
ECONSR = PID function on (SASP SAT)
CONSTANT VOLUME UNITS WITH SENSORS:
ECONSR = PID function on (set point SPT), where:
set point = (OCSP+OHSP/2, when OATL<OAT<68
set point = OCSP 1, when OAT OATL
set point = OHSP + 1, when OAT 68
VARIABLE AIR VOLUME UNITS:
ECONSR = PID function on (SASP + RESET SAT)
where RESET is the greater of Space Temperature
Reset Value or External SAT Reset.
ECONOMIZER CONTROL SUBMASTER LOOP (CCN/
Remote Start/Stop Only) The Economizer Control Sub-
master inputs and outputs are shown in Tables 11 and 12.
Table 11 Economizer Control
Submaster Loop Inputs
INPUTS TYPE
Fan State Internal Parameter
Economizer Submaster ref.
(ECONSR)
Internal Parameter
Supply-Air Temperature (SAT) Analog Input
Outdoor-Air Temperature (OAT) Analog Input
IQMP (minimum position) Internal Parameter
Current Mode Internal Parameter
ESG (Submaster Gain Limit) User Configured, default = -7.5
TEMPBAND
(OAT Temperature Band)
User Configured, default = 25
ECOBAND
(Damper Movement Band)
User Configured, default = 0
CTRVAL
(Damper Center Value)
User configured, default = 70
Table 12 Economizer Control
Submaster Loop Outputs
OUTPUTS TYPE
ECONPOS Economizer Damper Position %
Sequence of Operation
1. If a compressor is on and the economizer is usable, the
dampers will be open 100% and the rest of the sequence
of operation is omitted.
2. If the indoor fan is off (or has been on for less than
30 seconds), the supply-air temperature reading is not avail-
able, or the HEAT mode is active, the economizer posi-
tion (ECONPOS) will be at the minimum position (IQMP).
The rest of the sequence of operation is omitted.
3. If the OAT reading is available and the OAT <45 F, the
rate of damper movement will be limited to 1% every
4 seconds. Rate limiting will be stopped (allowing damp-
ers to go to the commanded position 1% every 0.9 sec-
onds) when the OAT 46 F.
4. This loop will adjust its Submaster Gain with changes in
outdoor-air temperature.
11