Smoke Control Modes — Variable air volume units
and CV units with optional expansion I/O board will per-
form fire and smoke control. The unit will provide 4 differ-
ent modes which can be used to control smoke within the
area serviced by the unit. These modes of operation are fire
shutdown, pressurization, evacuation, and smoke purge.
Each mode must be energized individually via channels
5, 6, 7, and 8 on the expansion board. The corresponding
alarm will be initiated when a mode is activated. The fire
system will provide a normally closed dry contact closure.
Table 43 specifies all actions the control will undertake
when each mode occurs (all outputs are forced with
priority 1 — Fire).
If more than one input is energized, the control will op-
erate in Fire Shutdown mode.
Head Pressure Control — The DDC module con-
trols the condenser fans to maintain proper head pressure.
The condenser fans are configured to react to the outdoor-air
temperature. On size 024-034 units, fan no. 2 is energized at
65 F and deenergized at 55 F. On size 038-048 units fans
no. 3 and no. 4 are energized at 65 F and deenergized at
55 F. On size 054-068 units, fans no. 3 through 6 are ener-
gized at 65 F and deenergized at 55 F. The leading fan (no.
1) can also be controlled with a Motormaster® III control.
On size 038-068 units, fan no. 2 operates at full speed with
a Motormaster control on fan no. 1.
Space Temperature Sensors
ACCESSORY SPACE TEMPERATURE SENSOR (T-55) —
The T-55 (Carrier part no. CEC0121448-01) sensor is a wall-
mounted device used to measure space temperature and for
unoccupied heating and cooling operation. It should be
installed as a wall-mounted thermostat would be (in the con-
ditioned space where it will not be subjected to either a cool-
ing or heating source or direct exposure to sunlight, and 4 to
5 ft above the floor). The sensor can also be used to override
the occupancy schedule in the unit by pushing the override
button on the front of the sensor.
ACCESSORY SPACE TEMPERATURE SENSOR (T-56) —
The T-56 sensor operates the same as the standard T-55 sen-
sor but has an additional feature of allowing the user to change
the set point ±5° F from the space temperature. The T-56
sensor (Carrier Part No. CEC0121503-01) is applicable to
CV and heat pump applications only. A slide potentiometer
is used to provide the space temperature offset and is located
on the face of the device. The sensor is a wall-mounted de-
vice and should be installed as a wall-mounted thermostat
would be (in the conditioned space where it will not be sub-
jected to either a cooling or heating source or direct expo-
sure to sunlight, and 4 to 5 ft above the floor). The sensor
can also be used to override the occupancy schedule in the
unit by pushing the button on the front of the sensor.
SPACE TEMPERATURE AVERAGING — Applications that
require averaging using multiple space temperature sensors
can be satisfied using either 4 or 9 sensors. Only Carrier sen-
sors may be used for standard T-55 space temperature av-
eraging. Sensors must be used in multiples of 1, 4 and 9
only, with total sensor wiring not to exceed 1000 ft.
NOTE: Space temperature reset can be accomplished with
only one sensor (provided standard with unit). Do not use
T-56 sensor for space temperature averaging because the
5° F offset function will not work in a multiple sensor
application.
Table 43 — Fire/Smoke Control Modes
DEVICE PRESSURIZATION
SMOKE
PURGE
EVACUATION
FIRE
SHUTDOWN
Economizer 100% 100% 100% 0%
Indoor Fan/VFD ON ON OFF OFF
Power Exhaust
(all outputs)
OFF ON ON OFF
Heat Stages OFF OFF OFF OFF
HIR ON ON OFF OFF
LEGEND
HIR — Heat Interlock Relay
VFD — Variable Frequency Drive
1
2
1
2
3
4
1
2
3
4
5
6
CONTROL
BOX
CONTROL BOX
CONTROL BOX
024-034 UNITS 038-054 UNITS 058-058 UNITS
Fig. 5 — Condenser-Fan Motor Locations