Submaster Gain is calculated as:
SubGain = (OAT TEMPBAND)/(ESG + 1);
SubGain is fixed between ESG and −1. The commanded
position is calculated as:
ECONPOS = SubGain x (ECONSR SAT) + CTRVAL
5. The ECONPOS is fixed between Minimum and Maxi-
mum Economizer Positions. Maximum Position is 100%
under normal conditions. When ‘rate limiting’ is in
effect under low ambient conditions, the Maximum Po-
sition is held to 1% above the last ECONPOS for 4 sec-
onds. This results in dampers opening slowly. Similarly,
Minimum Position is IQMP under normal conditions,
and is lowered by 1% every 4 seconds during ‘rate
limiting.’
6. If the new calculated ECONPOS is varied from the last
Economizer Position by less than ECONBAND, it will
ignore the new value and the dampers do not move.
Heating Control (CCN and Remote Start/Stop
Only)
HEATING CONTROL (Version 1.0 and 2.0 of the Control
Software)
Heating Control Master Loop The Heating Control Mas-
ter Loop inputs and outputs are shown in Tables 13 and 14.
Table 13 Heating Control Master Loop Inputs
(Version 1.0 and 2.0 of the Control Software)
INPUTS TYPE
Unit Type User Configured
Current Mode Internal Parameter
Fan State Internal Parameter
Occupied Status Internal Parameter
Space Temperature (SPT) Analog Input
Return-Air Temperature
(RAT)
Analog Input
Occupied Heating Option
(OHEN)
User Configured, default disabled
Occupied Heating Set Point
(OHSP)
User Configured, default = 68 F
Space Temperature Offset
(STO)
Analog Input
Morning Warm-up Status Internal Parameter
SAT Reset Internal Parameter
LEGEND
SAT Supply-Air Temperature
Table 14 Heating Control Master Loop Outputs
(Version 1.0 and 2.0 of the Control Software)
OUTPUTS TYPE
SHSR Submaster Reference Desired Supply-Air Temperature
Constant Volume Units Heating will maintain space tem-
perature at the unoccupied heat set point during unoccupied
periods, or occupied heat set point during occupied periods.
Variable Air Volume Units Heating control will maintain
return-air temperature at occupied heat set point under the
following conditions:
Units with space thermistor: unit is started during the un-
occupied period by the DDC control due to space tem-
perature falling below the unoccupied heat set point.
Unit is in morning warm-up mode: see Temperature Com-
pensated Start section on page 18.
Unit has Occupied Heating enabled: heating control will
maintain return-air temperature at occupied heat set point
during occupied periods.
Qualifying Conditions When all of the following condi-
tions are met, the submaster reference is calculated, other-
wise it is set to its minimum value:
Indoor fan has been ON for 30 seconds.
Cool mode is NOT active.
Occupied, Temperature Compensated Start, or Heat mode
is active.
VAV units: RAT reading is available.
CV units: SPT reading is available.
VAV units: Unoccupied mode, Morning Warm-Up or OHEN
option enabled and RAT<OHSP SAT Reset.
Sequence of Operation The Staged Heat Submaster Ref-
erence (SHSR) is calculated as follows:
SHSR = PID function on (error term)
For CV units:
error term = OHSP + STO (SAT Reset)
Space Temperature
For VAV units:
error term = OHSP (SAT Reset)
Return-Air Temperature
Morning Warm-Up (VAV Only) Morning warm-up is a
condition in VAV systems that occurs when the temperature
compensated start algorithm has calculated a biased occu-
pied start time, and the unit has a heating demand (i.e., RAT
< occupied heating set point). The Linkage mode warm-up
will be transmitted to the Linkage Supervisory POC device
to support DAV. The warm-up will continue into the occu-
pied period as long as there is a need for heat. During warm-
up, the unit can continue heating into the occupied period,
even if occupied heating is disabled. When the heating de-
mand is satisfied, the warm-up condition will terminate.
HEATING CONTROL (Version 3.0 Software)
Heating Control Master Loop The Heating Control Mas-
ter Loop inputs and outputs are shown in Tables 15 and 16.
Table 15 Heating Control Master Loop Inputs
(Version 3.0 Software)
INPUTS TYPE
Unit Type User Configured
Current Mode Internal Parameter
Fan State Internal Parameter
Occupied Status Internal Parameter
Occupied Heating Option
for VAV
DIP switch no. 5
Morning Warm-Up Status Internal Parameter
Space Temperature (SPT) Analog Input
Return-Air Temperature (RAT) Analog Input
Occupied Heating Set Point
(OHSP)
User Configured, default = 68 F
Space Temperature Offset
(STO)
Analog Input
LEGEND
VAV Variable Air Volume
Table 16 Heating Control Master Loop Outputs
(Version 3.0 Software)
OUTPUTS TYPE
SHSR Submaster Reference Desired Supply-Air Temperature
LEGEND
SHSR Staged Heat Submaster Reference
Constant Volume/Heat Pump Units Heating will maintain
space temperature at unoccupied heat set point during un-
occupied periods, or occupied heat set point during occu-
pied periods.
12