
Sequence of Operation (Expansion Module) —
For CV, VAV, or heat pump units equipped with optional ex-
pansion I/O (input/output) board, the following functions will
be added to the sequence:
1. The expansion control board will perform a periodic SIO
scan and maintain I/O database expanded I/O points.
2. Fire/Smoke Control is performed.
3. If the unit is in Occupied mode (or indoor fan is ON for
thermostat units), the expansion control board will per-
form IAQ control.
4. The fan, filter, demand limit, and field-applied status is
monitored.
OPERATION
Constant Volume Operation with Thermostat —
Although these units are designed for operation with room
sensors configured with an occupancy schedule and CCN
compatible for comfort heating and cooling, the unit is also
compatible (without additional hardware) with a two-stage
heat and two-stage cool thermostat. Thermostat inputs and
outputs are shown is Tables 1 and 2.
Table 1 — Thermostat Operation Inputs
INPUTS TYPE
TSTAT DIP switch no. 2
Heat Type DIP switch no. 7
AC/Heat Pump DIP switch no. 8
G Discrete Input
Y1 Discrete Input
Y2 Discrete Input
W1 Discrete Input
W2 Discrete Input
Enthalpy Switch Discrete Input
Supply-Air Temperature (SAT) Analog Input
Outdoor-Air Temperature (OAT) Analog Input
Minimum Position (IQMP) Internal Parameter
Supply-Air Set Point (SASP) User Configured
(default = 55 F)
High OAT Economizer Lockout (OATL) User Configured
(default = 65 F)
Table 2 — Thermostat Operation Outputs
OUTPUTS TYPE
Thermostat Operation Mode Internal Parameter
Indoor Fan Discrete Output
Compressor 1 Discrete Output
Compressor 2 Discrete Output
Economizer Position Analog Output
Heat 1 Discrete Output
Heat 2 Discrete Output
THERMOSTAT OPERATION MODE — The thermostat mode
is only operational on CV or heat pump units. If the DIP
switch is set for thermostat operation, the control will set
Thermostat Operation mode (TSTAT) and clear all other modes.
In Thermostat Operation mode the function of the control
will be limited. See Fig. 1 and 2.
Indoor Fan — When in Thermostat Operation mode, the in-
door fan will operate in the following way:
• when G input is energized, turn on indoor fan and open
economizer dampers to the minimum position (IQMP)
• when G input is deenergized, turn off the indoor fan and
close the economizer dampers.
• when the unit has electric heat or is a heat pump, turn on
the indoor fan whenever there is a call for heat.
For a further explanation of the economizer damper mini-
mum position (IQMP) see the Indoor-Air Quality Sequence
of Operation section on page 15.
Cooling — When in Thermostat Operation mode, the G ter-
minal must be energized before cooling can operate. When
G is initiated and there is no call for cooling, the economizer
will be at the minimum position (IQMP).
The control will determine if outdoor conditions are suit-
able for economizer cooling. The conditions are suitable when:
• Enthalpy is low
•OAT≤OATL (see Table 1)
• SAT reading is available
• OAT reading is available
When all 4 of the above conditions are satisfied, the con-
trol will use the economizer as the first stage of cooling. When
Y1 input is energized, the economizer will modulate to main-
tain SAT at the Supply-Air Set Point (SASP). When SAT is
above SASP, the economizer will be 100% open. When SAT
is below SASP the economizer may modulate between mini-
mum position and 100%. When Y2 is energized, and SAT is
less than SASP, the control will bring on compressor no. 1
and continue modulating the economizer as described above.
If SAT remains above SASP for 15 minutes, compressor no.
2 will be started. When Y2 is deenergized, the last stage of
compression will be dropped. When Y1 is deenergized, the
control will drop all DX cooling, and drive the economizer
to the minimum position if the thermostat fan switch is in
the ON position, or will close it if the thermostat fan switch
is in the AUTO position.
If the outdoor conditions are not suitable, the control will
keep the economizer at the minimum position and cycle com-
pressor no. 1 and 2 based upon Y1 and Y2 respectively.
The control will lockout the compressors if the SAT is too
low: compressor no. 1 lockout at SAT <40 F and compres-
sor no. 2 lockout at SAT <45 F.
After a compressor is locked out, it may be restarted again
after a normal time guard period.
Heating — When in Thermostat Operation mode, the in-
door fan must be on for electric heat. Heat 1 will follow W1
input. Heat 2 will follow W2 input. Heating and cooling
will be mutually locked out based on which mode was ini-
tiated first.
Heating (Heat Pump) — When in Thermostat Operation mode,
the indoor fan will be on. Compressor no. 1 and 2, and re-
versing valve solenoids 1 and 2 will follow W1 input. Heat
stages 1 and 2 will follow W2 input. The unit will follow
calls for defrost with timed defrost cycles.
Heating and cooling will be mutually locked out based on
which mode was initiated first. The control will maintain com-
pressor time guards and safety checks at all times.
5
Comentarios a estos manuales