• control of one stage of gas or electric heat to maintain supply-
air temperature at supply-air set point during occupied
periods
• ability to use multiple space temperature sensors to aver-
age space temperature
• support linkage function for interface with DAV (Digital
Air Volume) systems
• enable heating or cooling during unoccupied periods as
required
• provide space temperature reset to reset the supply-air set
point upward when temperature falls below its occupied
cooling set point (space temperature sensor is required)
• provide space temperature reset to reset the supply air set
point upward from a remote 4 to 20 mA signal
• provide VFD (variable frequency drive) enable high volt-
age relay output to enable VFD
• control of heat interlock relay
Standard Heat Pump Only Features
• control compressors and reversing valve solenoids as first
stage of heating
• control heat stages 1 and 2 as second stage heating or as
emergency heat
• control of both outdoor fans during heating
• provide defrost cycles during heating
Accessory Expansion Board Features
• control of modulating economizer damper to maintain
indoor-air quality when outdoor conditions are suitable
• provide discrete inputs for fan status, filter status, field
applied status, and demand limit
• provide demand limit functions based upon the state of
the discrete input
• provide an output for the external alarm light indicator
• smoke control modes including evacuation, smoke purge,
pressurization, and fire shutdown
• provide power exhaust fire outputs for direct control of
modulated power exhaust stages during fire/smoke modes
INPUTS/OUTPUTS AND
SYSTEM INFORMATION
The DDC board contains the factory-loaded software that
monitors and processes the following inputs, outputs and sys-
tem information:
• INPUTS:
− thermistors
− switches
− remote 4 to 20 mA signal
• OUTPUTS (CV OPERATION):
− condenser fan contactors
− indoor-fan relay
− compressors stages 1 and 2
− crankcase heaters
− heat stages 1 and 2 operation
− economizer motor (4 to 20 mA)
− optional non-modulating power exhaust
− optional modulating power exhaust enable
• OUTPUTS (VAV OPERATION):
− condenser fan contactors
− indoor-fan relay/variable frequency drive enable
− compressors and unloading stages 1 through 6
− crankcase heaters
− heat relay
− heat interlock relay
− economizer motor (4 to 20 mA)
− optional non-modulating power exhaust (Version
3.0 software)
− optional modulating power exhaust enable
• OUTPUTS (HEAT PUMP OPERATION):
− condenser fan contactors
− indoor-fan relay
− compressors stages 1 and 2
− crankcase heaters
− heat stages 1 and 2 operation
− economizer motor (4 to 20 mA)
− optional power exhaust
− reversing valve solenoids
− outputs to Y for defrost
• OUTPUTS (EXPANSION MODULE):
− alarm light
− power exhaust override
− smoke control modes
− IAQ/OAQ (indoor air quality/outdoor air quality) ven-
tilation modes
NOTE: Software resides in non-volatile memory in the DDC;
memory will not be lost with an extended power failure. There
are no batteries to replace over time.
• SYSTEM INFORMATION:
− generates alert and alarm information (via sensor
inputs)
− supports level II communications
− supports digital air volume (DAV) interface (48/
50EK,EY only)
− maintain service history
• ACCESSORY EXPANSION MODULE — The expan-
sion module is a field-installed accessory. Through input
and output channels on the module, it supports the sensors
and inputs used for:
− fan status
− filter status
− field applied status
− demand limit
− fire unit shutdown
− fire pressurization
− fire evacuation
− fire smoke purge
− IAQ/OAQ
Base Module — The base unit module closes contacts
to energize the compressors, crankcase heaters, and the evapo-
rator fan motor (CV or heat pump) or enable the variable
frequency drive (VAV). Triacs are used to energize the heat
relays, heat interlock relay (VAV), outdoor fans, compressor
unloaders (VAV), and reversing valve relays (HP), and en-
able the optional power exhaust. A room thermostat or room
sensor, optional outside air enthalpy, outdoor-air thermistor,
supply-air thermistors, and compressor switches (compres-
sor safety circuit) provide inputs to this module. When used
with a room sensor, a remote start/stop input can be used to
override the occupancy schedule.
Expansion Module — On the expansion module, the
triacs are used to turn on an alarm light, jumper the modu-
lating power exhaust sequencers, and force the power ex-
haust motors on when necessary in the fire/smoke mode. An
accessory fan status switch, accessory filter status switch,
accessory field applied status switch, an accessory indoor-
air quality switch, and an accessory outdoor-air quality switch
as well as accessory fire unit shutdown, pressurization, evacu-
ation and smoke purge switches provide input to the expan-
sion module. Demand limit can be provided through a 24-v
input.
Economizer — The DDC controls outputa4to20mA
signal to the actuator in the unit to modulate it as required
by the control algorithm. Damper is a spring-return type to
allow automatic closing of the damper on power loss.
3