Carrier 50EJQ Información técnica Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 44
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
this fault occurs 3 times within 90 minutes, the compressor
will be locked out and manual reset will be required. To re-
set, interrupt power to the control board. The possible causes
are:
1. High-pressure switch open. The high pressure switch is
wired in series with the control relay that energizes the
safety circuit. If the high-pressure switch opens during
compressor operation, the compressor stops, and the stop
is detected by the control board. The high pressure switch
will not lock out during the first 5 minutes of operation.
2. Low-pressure switch open. The low pressure switch is wired
in series with the control relay that energizes the safety
circuit. If the low-pressure switch opens during compres-
sor operation, the compressor stops, and the stop is de-
tected by the control board. The board ignores the low
pressure switch during the first 5 minutes of operation to
prevent nuisance stops if low ambient operation is
required.
3. Internal compressor protector open. The internal com-
pressor protector is used on 06D model compressor. The
internal protector switch is wired in series with the con-
trol relay that energizes the safety circuit. If the internal
protector switch opens during compressor operation, the
compressor stops, and the stop is detected by the control
board.
4. Freeze protection thermostat open. The freeze protection
thermostat switch is wired in series with the control relay
that energizes the safety circuit. If the freeze protection
thermostat switch opens during compressor operation, the
compressor stops, and the stop is detected by the control
board.
5. Wiring error. A wiring error in the control safety circuit
will cause the modules to malfunction, and an error will
be indicated.
Start the compressor. If the compressor starts, verify that
all stages of condenser fans are operational. Observe com-
pressor operation to verify that compressor is working and
condenser fans are energized after compressor starts.
ALARM CODE HF_15 (Thermostat Failure) This alarm
does not apply to a unit configured for and connected to a
space thermistor. If the thermostat is calling for heating and
cooling at the same time, the unit will operate on a ‘first
come first served’ basis and an alarm will be generated. An
alarm will also generate if stage 2 heating or cooling is called
for before stage 1. Reset of this alarm is automatic once the
problem is corrected. The cause of the alarm is usually a bad
thermostat, a wiring error, or a loose connection.
ALARM CODE HF_16 (Control Board Failure) This alarm
is generated with a faulty module. All outputs are turned off.
The module must be replaced.
If the analog to digital converter fails, the control board
will appear to operate correctly, however all set points will
revert back to default values in the event of a power failure.
The module must be replaced.
ALARM CODE HF_17 (Expansion I/O Board Failure)
This alarm is generated with a faulty module. If this is a
result of an analog to digital conversion, all outputs are turned
off and the unit shuts down. If this is a result of the non-
volatile RAM unable to read the set points, it will appear to
operate normally, however, in the event of a power failure,
the device will operate to the default values upon resump-
tion of power. The module must be replaced.
ALARM CODE HF_18 (Timeclock Failure) This alarm
is not used with CV units configured for and connected to a
thermostat. The alarm is generated when clock data is out of
range, or if the time does not advance. All outputs are turned
off. Reset is automatic.
ALARM CODE SE_05 (Loss of Communications with Ex-
pansion Board) If communication is lost with the expan-
sion board all algorithms involving the expansion board will
be bypassed, and an alarm will be generated. This alarm will
reset automatically when the communication is restored.
The outputs will turn on normally after the alarm condition
has been reset. The probable cause for this condition is a
faulty or improperly connected plug, a wiring error, or a faulty
module.
ALARM CODE SE_14 (Indoor-Air Quality Sensor Failure)
This alarm is valid only when the expansion board is used,
the IAQ alarm option is enabled, and the unit is equipped
with field-supplied IAQ sensors. The alarm is generated when
the IAQ sensor is reading less than one volt. The reset method
is automatic and the alarm is cleared when the sensor reads
at least 1.5 volts.
ALARM CODE SE_15 (Linkage Failure DAV System
Only) A linkage failure alarm is generated when the link-
age has stopped updating the TSM linkage tables within the
last 5 minutes.
NOTE: This alarm can only be generated after linkage has
updated the table at least one time since initialization.
The unit controls enter the linkage default mode if the link-
age is enabled, but the communications link has been lost.
With the controls having reverted back to stand-alone op-
eration, the existing sensors, previously overridden by link-
age, will be used. This may be caused by a loose connection
or a broken wire. Reset of this alarm is automatic once the
problem is corrected.
ALARM CODES SE_16 to SH_19 (Fire Shutdown, Smoke
Purge, Evacuation, Pressurization) When the unit is equipped
with an optional smoke control and a fire system is installed,
these 4 modes are provided to control smoke within areas
serviced by the unit. The unit must be equipped with an econo-
mizer, power exhaust, and the expansion module to support
these modes. The building fire alarm system closes field sup-
plied, normally open, dry contacts connected to the expan-
sion module to activate the alarms. Reset of this alarm is
automatic once the problem is corrected.
ALARM CODE SE_20 (Outdoor-Air Quality Sensor Fail-
ure) This alarm is valid only when the expansion board
is used, the OAQ alarm option is enabled, and the unit is
equipped with field-supplied OAQ sensors. The alarm is gen-
erated when the OAQ sensor is reading less than one volt.
The reset method is automatic and the alarm is cleared when
the sensor reads at least 1.5 volts.
ALARM CODE SE_21 (Supply-Air Thermistor Reset Fail-
ure) This alarm is valid only when enabled. This alarm is
generated when the supply-air temperature sensor is reading
less than one volt. The reset method is automatic and the
alarm is cleared when the sensor reads at least 1.0 volts. The
cause of the alarm is usually a bad thermistor, a wiring error,
or a loose connection.
ALARM CODE SE_22 (STO Sensor Failure) This alarm
is valid only when enabled. This alarm is generated when
the STO sensor is open or shorted for greater than 5 seconds.
Reset of this alarm is automatic once the problem is cor-
rected. The cause of the alarm is usually a bad thermistor, a
wiring error, or a loose connection.
DATA STORAGE ERRORS The control will also detect
data storage failures in Non-Volatile RAM, and generate Stor-
age Failure (SF) alarms as they occur. When storage failure
occurs, the following logic will take place. If ‘good’ value
of the failed configuration/service parameter is available in
RAM, it will be used until the next power-up, at which time
the parameter will be loaded with its default value. In case
of a Storage Failure occurring before RAM has been up-
dated, the default value will be loaded immediately. The stor-
age failure alarms will be enunciated on CCN only. The alarm
light or LED blinks are not used. Table 61 shows a complete
list of storage failure codes.
A controls troubleshooting table is provided for use in ser-
vicing the unit. See Table 62.
31
Vista de pagina 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 43 44

Comentarios a estos manuales

Sin comentarios