
Base and Expansion Board Modules — Table 44
is a map of the type of input and output for each channel and
corresponding terminal for both the base module as well as
the expansion module. Tables 45, 46, 47, and 48 indicate the
channel functions for the CV, heat pump, VAV, an d expan-
sion board, respectively. Tables 49 and 50 show the DIP switch
assignments for the control board.
Field Test — The field test program is initiated by mov-
ing DIP switch no. 4 to the ON position. The field test
sequence will start. The first sequence will close the outdoor-
air damper. The control allows 90 seconds for the damper to
close in case it is in the full open position. Next, the indoor
fan contactor is energized and the outside air damper begins
to open to its default value of 20%and stays at that position
for a short period of time. The outdoor-air damper will then
open to its full open position and again stay at that position
for a short period of time. Then the outdoor-air damper will
then close.
If the unit is equipped with power exhaust, stage 1 will be
energized for 5 seconds. If the unit is configured for stage
two of power exhaust, it will be energized for 5 seconds af-
ter the first stage is deenergized.
The next step will energize the first stage of heat for
30 seconds, after which time the second stage heat will be
energized for an additional 30 seconds. Heat is then
deenergized.
The last step will run the Cooling mode. Outdoor fan
contactor no. 1 is energized. This is followed by each stage
of cooling energized with a 10 second delay between stages.
Next outdoor fan contactor no. 2 is energized for
10 seconds.
The compressors will now deenergize followed by the out-
door fan contactors and indoor fan contactors. If the unit is
equipped with the Integrated Gas Control (IGC) board, the
indoor fan will continue to operate for an additional 30 sec-
onds after deenergizing the circuit.
The field test is complete.
Factory Test (Software Version 1.0 Only) — A
factory test (with DIP switch no. 8) was used only with Ver-
sion 1.0 software.
The Factory Test DIP switch should not be enabled in
the field.
The factory/operational test is manually executed using a
Personal Computer program that reads inputs and control out-
puts via CCN communications. Before the test is run, the
unit will be placed in Factory Test mode by turning DIP
switch no. 8 to the Test position. As the switch is put into the
test position, all outputs will be turned off. The DDC will
now be ready to receive test commands from CCN. When
the factory test mode is initiated, a one-hour timeout timer
will be started by the DDC to prevent the unit from remain-
ing in that mode for more than one hour.
The factory test mode will be turned off when switch 8is
switched off or when the one hour timer expires, which-
ever comes first. The factory test has been eliminated in Soft-
ware Version 2.0 and 3.0.
Table 44 — Input/Output Points
CHANNEL NO.
(TERMINALS)
INPUT TYPE OUTPUT TYPE
CHANNEL NO.
(TERMINALS)
INPUT TYPE OUTPUT TYPE
1 (T17-T25) 24 Volt — 18 (T28-T29) — 24 or 115 Volt
2 (T18-T25) 24 Volt — 19 (T30-T29) — 24 or 115 Volt
3 (T19-T25) 24 Volt — 20 (T31-T32) — 24 or 115 Volt
4 (T20-T25) 24 Volt — 21 (T33-T32) — 24 or 115 Volt
5 (T21-T25) 24 Volt — 22 (T34-T35) — 24 or 115 Volt
6 (T22-T25) 24 Volt — 23 (T36-T35) — 24 or 115 Volt
7 (T23-T25) 24 Volt — 24 (T37-T38) — 24 or 115 Volt
8 (T24-T25) 24 Volt — 25 (T39-T38) — 24 or 115 Volt
9 (T1-T2) 10K Resistor — 26 (K1, N.O.) — SAME AS K1, COM
10 (T3-T4) 5 or 10K Resistor — (K1, N.C.) — SAME AS K1, COM
11 (T5-T6) 5K Resistor — (K1, COM) 24, 115 or 230 Volt —
12 (T7-T8) 5K Resistor — 27 (K2, N.O) — SAME AS K2, COM
13 (T9-T10) Resistor (TBD) — (K2, N.C.) — SAME AS K2, COM
14 (T11-T12) 4-20mA — (K2, COM) 24, 115 or 230 Volt —
15 (T13-T14) 4-20mA — 28 (K3, N.O.) — SAME AS K3, COM
16 (T15-T16) 4-20mA — (K3, N.C.) — SAME AS K3, COM
17 (T26-T27) — 4-20mA (K3, COM) 24, 115 or 230 Volt —
NOTE: For terminals witha4to20mAsignal, odd numbered terminals are (+), even terminals are (−).
21
Comentarios a estos manuales