11
4.9.4 - SETPOINT menu
roomtocc 15 to 30 21.05 °C Room temperature setpoint in occupied mode
roomtuno 5 to 35 28 °C Room temperature setpoint in unoccupied mode
satmin 10 to 18 14 °C Minimum supply air temperature
satmax 25 to 35 30 °C Maximum supply air temperature
potreset 0 to 3 3 ^C Maximum room air setpoint reset
oat1_cor -20 to 14 -10 °C OAT threshold 1
corlooat -5 to 0 -2 ^C Correction if OAT < oat1
oat2_cor 15 to 35 30 °C OAT threshold 2
corhioat 0 to 5 2 ^C Correction if OAT > oat2
oat_cor No/Yes no - Setpoint reset based on OAT
lim_sp1 0 to 100 100 % Capacity limit 1
lim_sp2 0 to 100 100 % Capacity limit 2
lim_sp3 0 to 100 100 % Capacity limit 3
4.9.5 - INPUTS menu
ONOFF_SW Open/Closed - Indoor fan reversal, start/stop
STAGE_1 Open/Closed - Contact stage 1
STAGE_2 Open/Closed - Contact stage 2
STAGE_3 Open/Closed - Contact stage 3
STAGE_4 Open/Closed - Contact stage 4
LOCK Alarm/Normal - Customer contact status (safety loop)
AL_RESET Open/Closed - Alarm reset demand
HC_SW Open/Closed - Remote contact for heating/cooling mode selection (not used)
on_ctrl - - Current control
SP_SW Open/Closed - Remote contact for setpoint 1 selection, occupied mode
LIM_SW1 Open/Closed - Status limit contact 1 (not used)
LIM_SW2 Open/Closed - Status limit contact 2 (not used)
OCC_SW Open/Closed - Start of occupied mode
4.9.6 - OUTPUTS menu
CP_A1 On/O - Output compressor 1
CP_A2 On/O - Output compressor 2
CP_A3 On/O - Output compressor 3
fan_a1 - - Fan output A1
fan_a2 - - Fan output A2
HD_POS_A - % Fan variator output A
RV_A On/O - Four-way valve
LLS_A1 Closed/Open - Liquid line valve A1
LLS_A2 Closed/Open - Liquid line valve A2
CP_B1 On/O - Output compressor 1
CP_B2 On/O - Output compressor 2
fan_b - - Fan output B
HD_POS_B - % Fan variator output B
RV_B On/O - Four-way valve
LLS_B1 Closed/Open - Liquid line valve B1
LLS_B2 Closed/Open - Liquid line valve B2
IN_FAN On/O - Indoor fan control
ALRM_LED On/O - Alarm LED status
ALARM On/O - Alarm relay status
RUNNING On/O - Unit operation status
4.9.7 - RUNTIME menu
hr_mach - hours Number of unit operating hours
st_mach - - Number of start-ups, unit
HR_CP_A1 - hours Number of operating hours compressor A1
st_cp_a1 - - Number of start-ups compressor A1
HR_CP_A2 - hours Number of operating hours compressor A2
st_cp_a2 - - Number of start-ups compressor A2
HR_CP_A3 - hours Number of operating hours compressor A3
st_cp_a3 - - Number of start-ups compressor A3
HR_CP_B1 - hours Number of operating hours compressor B1
st_cp_b1 - - Number of start-ups compressor B1
HR_CP_B2 - hours Number of operating hours compressor B2
st_cp_b2 - - Number of start-ups compressor B2
hr_fana1 - hours Number of operating hours fan 1, circuit A
hr_fana2 - hours Number of operating hours fan 2, circuit A
hr_fanb1 - hours Number of operating hours fan, circuit B
st_fana1 - - Number of start-ups fan 1, circuit A
st_fana2 - - Number of start-ups fan 2, circuit A
st_fanb1 - - Number of start-ups fan 1, circuit B
nb_def_a - - Number of defrost cycles, circuit A (not used)
nb_def_b - - Number of defrost cycles, circuit B (not used)