Carrier Pro-Dialog CONTROL 4 Manual de usuario Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
18





   
1 th204 Room sensor thermistor fault Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor, thermistor not
connected, short circuit
Unit is shut down if this sensor is
used
2 se-01 Setpoint reset fault Automatic when the value returns to the
normal range
Potentiometer not connected,
potentiometer resistance too high
Setpoint reset is no longer
available
3 th-12 Suction temperature sensor
fault, circuit A
Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor, thermistor not
connected, short circuit
Superheat monitoring is no
longer available for this circuit
4 th-13 Suction temperature sensor
fault, circuit B
Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor, thermistor not
connected, short circuit
Superheat monitoring is no
longer available for this circuit
5 th-03 Defrost sensor fault, circuit A
(not applicable to the control)
Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor, thermistor not
connected, short circuit
Unit is shut down if this sensor is
used
6 th-04 Defrost sensor fault, circuit B
(not applicable to the control)
Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor, thermistor not
connected, short circuit
Unit is shut down if this sensor is
used
7 th-10 Outdoor temperature sensor
fault
Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor, thermistor not
connected, short circuit
Unit is shut down if this sensor is
used
8 th202 Supply air thermistor fault Automatic when the temperature measured
by the sensor returns to normal
Defective thermistor, thermistor not
connected, short circuit
Unit is shut down if this sensor is
used
9 Pr-01 Discharge pressure sensor
fault, circuit A
Automatic when the voltage transmitted by
the sensor returns to normal
Defective thermistor or wiring fault Circuit is shut down
10 Pr-02 Discharge pressure sensor
fault, circuit B
Automatic when the voltage transmitted by
the sensor returns to normal
Defective thermistor or wiring fault Circuit is shut down
11 Pr-04 Suction pressure sensor fault,
circuit A
Automatic when the voltage transmitted by
the sensor returns to normal
Defective thermistor or wiring fault Circuit is shut down
12 Pr-05 Suction pressure sensor fault,
circuit B
Automatic when the voltage transmitted by
the sensor returns to normal
Defective thermistor or wiring fault Circuit is shut down
13 Co-O1 Communication loss with
auxiliary board 1
Automatic when communication is
re-established
Defective auxiliary board or wiring fault Depending on conguration,
compressor A3 shut down, circuit
B shout down or unit shut down
14 CoDr1 Communication loss with
frequency variator of fan 1
Automatic when communication is
re-established
Defective variator or wiring fault The circuit using this fan is shut
down
15 CoDr2 Communication loss with
frequency variator of fan 2
Automatic when communication is
re-established
Defective variator or wiring fault The circuit using this fan is shut
down
16 FC-01 Illegal factory conguration
number 1 to nn
Automatic when a correct conguration is
entered
Incorrect conguration Unit is shut down
17 FC-nO No factory conguration Automatic when a correct conguration is
entered
No conguration (unit size) Unit is shut down
18 P-05 Low suction temperature, circuit
A
Automatic when the temperature returns to
normal, and if this alarm has not appeared
during the last 24 hours, otherwise manual.
Defective pressure sensor, TXV
blocked or refrigerant charge too low
Circuit is shut down
19 P-06 Low suction temperature, circuit
B
Automatic when the temperature returns to
normal, and if this alarm has not appeared
during the last 24 hours, otherwise manual.
Defective pressure sensor, TXV
blocked or refrigerant charge too low
Circuit is shut down
20 P-11 Low superheat, circuit A Manual Defective sensor, TXV blocked Circuit is shut down
21 P-12 Low superheat, circuit B Manual Defective sensor, TXV blocked Circuit is shut down
22 P-16 Compressor A1 not started or
no pressure increase registered
Manual Defective compressor or wiring fault Compressor is shut down
23 P-17 Compressor A2 not started or
no pressure increase registered
Manual Defective compressor or wiring fault Compressor is shut down
24 P-18 Compressor A3 not started or
no pressure increase registered
Manual Defective compressor or wiring fault Compressor is shut down
25 P-20 Compressor B1 not started or
no pressure increase registered
Manual Defective compressor or wiring fault Compressor is shut down
26 P-21 Compressor B2 not started or
no pressure increase registered
Manual Defective compressor or wiring fault Compressor is shut down
27 P-204 No air ow or customer safety
loop open
Manual Safety loop open, pressure switch fault,
air ow or wiring fault
Unit is shut down
28 P-31 Unit emergency stop CCN An emergengy stop command has
been issued by the CCN
Unit is shut down
29 P-37 Repeated overrides, high
discharge temperature, circuit
A
Automatic Defective transducer, condenser air
temperature too high, condenser
fouled or fan air ow too low.
Signalling
30 P-38 Repeated overrides, high
discharge temperature, circuit
B
Automatic Defective transducer, condenser air
temperature too high, condenser
fouled or fan air ow too low.
Signalling
31 P-40 Repeated exceeded low
suction temperature, circuit A
Automatic Defective pressure sensor or
refrigerant charge too low
Circuit is shut down
32 P-41 Repeated exceeded low
suction temperature, circuit B
Automatic Defective pressure sensor or
refrigerant charge too low
Circuit is shut down
33 P-63 High pressure switch fault,
circuit A
Manual and the high pressure switch must
be manually reset
Fan circuit fault, air or condenser
temperature too high
Circuit is shut down
34 P-64 High pressure switch fault,
circuit B
Manual and the high pressure switch must
be manually reset
Fan circuit fault, air or condenser
temperature too high
Circuit is shut down
35 P-100 Incorrect indoor fan status Automatic Thermostat transmits a cooling stage
demand when the indoor fan is shut
down
Unit is shut down
36 V0-xx Fan voltage variator fault, circuit
A
Manual or automatic Variator fault or alert Alert: circuit continues to operate,
variator slows the motor down
Alarm: circuit is shut down
37 V1-xx Fan voltage variator fault, circuit
B
Manual or automatic Variator fault or alert Alert: circuit continues to operate,
variator slows the motor down
Alarm: circuit is shut down